Samsung DH60 T Series Installation Manual page 13

System air conditioner
Table of Contents

Advertisement

Wiring Diagram (DH48GTA, DH60GTA, DC48GTA, DC60GTA)
MAIN PCB
Float Switch
Drain Pump
(Optional)
1(L) 2(N)
Vc
Power
F1
Cable Specifications
The following electrical characteristics must be respected.
MODEL
Power
Circuit breaker
Indoor unit power cable
Communication cable
Wired remote controller power
& communication cable
20m or less
Power cable
50m or less
Receiver &
Display Unit
(Optional)
Indoor Unit
Vc
Vw Vw
F1
F2
V1
Communication
F2
Outdoor Unit
DH48GTA(X), DH60GTA(X), DC48GTA(X), DC60GTA(X)
3ø 380-415V~, 50Hz
20A
1.25mm
2
(CV, 3 wire)
0.75~1.0mm
2
(CV, 2 wire)
0.5~0.75mm
2
(CV, 2 wire)
2.0mm
2
(CV, 5 wire)
2.5mm
2
(CV, 5 wire)
V2
F3
F4
Wired
Remote
Controller
The power cables are not
supplied with the air
conditioner.
The user should purchase
them separately.
MAIN POWER
3
380 - 415V~, 50H
ø
z
Note
13