Clearances - Lennox Bella Installation And Operation Manual

Free-standing pellet stove country collection
Table of Contents

Advertisement

0*" (0 mm)
3"
(76mm)
Min.
Floor Protector
*Note: Refer to Page 4 for chimney/venting floor protection
requirements and recommendations.
Figure 1 - Floor Protection Requirements

CLEARANCES

Standard residential or manufactured home installation. These appliances
require the following minimum clearances to combustibles:
Minimum Clearances To Combustibles
IMPORTANT
• Minimum clearances specified may not allow
for ease of operation and maintenance (please
take this in to account when planning the instal-
lation). If installed to the minimum clearances,
removal of the appliance may be necessary for
servicing.
• Recommended clearance zone from the front of the
appliance to combustibles is 4 feet minimum.
• Clearances to combustibles for the appliance
can only be reduced by means approved by the
regulatory authority.
Back
3"
Top View
(76mm)
Min.
Front
6" (15mm) Min.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE
Corner Installations - Clearance to Combustibles
Combustible Wall
3*"
(76mm)
3-1/"
(89mm)
*Note: Refer to pipe Manufacturer's installation instructions
for minimum pipe clearances.
Figure 2 - Left Wall Horizontal Venting
3*"
(76mm)
Combustible Wall
3-1/"
(89mm)
*Note: Refer to pipe Manufacturer's installation instructions
for minimum pipe clearances.
Figure 3 - Right Wall Horizontal Venting
3-1/" (89mm)
Top View
3-1/" (89mm)
Top View
5