Hydro Unit
0 = Contacts low > high
system stop. System restart
with remote controller
1 = Contacts high > low
system stop. System restart
with remote controller
2 = Contacts high > low
system stop. Contacts low >
high system restart
3 = Contacts low > high
system stop. Contacts low >
high (second time) system
E-Stop Switch
21
restart
Logic
0 = Restart hot water and
heating
1 = Restart in the mode when
stopping
2 = Restart heating
3 = Restart hot water
4 = Tempo control 1; without
heater
5 = Tempo control 2; without
HP and heater
0012 = 80*XWH**E
0017 = 140*XWH**E
Factory set but function code
Hydro Unit
22
is needed for PCB
Capacity Setting
replacement or function code
reset procedure has been
completed.
Second Remote
Controller
0=Water temperature
23
Target
1=Room thermo temperature
temperature
Setting
Room
Temperature shift for heating
24
Temperature
Temperature shift for cooling
Sensor Setting
Synchronization
0 = HP + Boiler
control at low
25
1 = Boiler
outside
2 = Backup heater
temperature
Settings by Purpose
Settings when hot water supply function is
not used
• When the hot water supply function is not used, set
DIP SW12-1 on the Hydro Unit board to ON. (Refer
to page 30.)
Setting for cooling
• For Hydro Units that do not perform cooling (those
for floor heating, etc.), procure a motorized 2-way
valve (for cooling) (refer to "Control parts
specifications" on page 21 for the details.) locally and
attach it to the water pipe that is not used for cooling.
Connect the valve cables to terminals TB05 (3) and
(4) of the Hydro Unit.
Location & FC
Number
FC Description
Hydro
52
61
01
40
5B
– 37 –
After
RC
Range
Default
Commissioning
0~3
0
0~5
0
Depends
0012 or
on Hydro
0017
Unit
0~1
0
02
-10~10
-1
03
-10~10
-1
0~2
0
• Press long the TEST
+ SET
switches on the remote controller to
change the Hydro Unit function code, and change
address 02 to 0, and then press the SET
to enable the function. Press the TEST
exit the setting mode.