+00EF99805101_01EN.book Page 30 Monday, June 21, 2010 3:45 PM
Hydro Unit
• Set DIP SW2 to ON (Room temperature) on the
remote control which you will control the room
temperature with.
DIP SW2 of optional remote control is preset to ON
(Room temperature).
Either one of header or second remote control must
be set as room temperature control.
• To control room temperature instead of water
temperature with this remote control, set function
code "40" of hydro unit to "1".
8

START UP AND CONFIGURATION

Set the DIP switches and function codes.
Setting DIP Switches on the Board in the Hydro Unit
• Detach the front cover and the electric parts box cover of the Hydro Unit.
• Set the DIP switches on the main board.
▼ Fig. 8-01
SW No.
DIP No.
Boiler install location
1
OFF = Heating side after 2 way valve
ON = Before 3 way valve
2
Not Used
02
3
Not Used
Used to when an external room thermostat is
connected
4
OFF = No external room thermostat;
ON = External room thermostat connected
P1 Pump operation for hot water
1
OFF = synchronised with heat pump
ON = Normally run
P1 Pump operation for heating
2
OFF = Normally run
ON = Stopped at the outside temperature over 20°C
10
Synchronisation of Pump P2.
OFF = P2 continuous operation(pump off when
3
remote controller switched off)
ON = P1 synchronised with pump P1
4
Not Used
SW10
SW11
ON
ON
ON
1
2
3
4
1
2
3
OFF
Description
– 30 –
SW12
SW13
ON
ON
4
1
2
3
4
1
2
3
After
Default
Change 1 Change 2 Change 3
Commissioning
OFF
OFF
OFF
OFF
OFF
Installation Manual
4
Toshiba XXXXXXX(<SanSerif1>X/X)