Using Offsets/Returns - Heat & Glo Montana-36 Owner's Manual

Woodburning fireplace
Hide thumbs Also See for Montana-36:
Table of Contents

Advertisement

B. Using Offsets/Returns
To bypass any overhead obstructions, the chimney may be
offset using an offset/return.
An offset and return may be attached together or a chimney
section(s) may be used between an offset and return.
Perform the following steps to determine the correct chim-
ney component combination for your particular installation:
WARNING
Fire Risk
Draft will be restricted if offsets/returns
greater than 30° are used.
Table 5.2
A
B
in.
mm
in.
4 7/8
124
17 7/8
7 1/4
184
2 2
9 3/4
248
26 1/8
10 1/4
260
27 1/4
12 3/4
324
31 3/8
13 1/4
337
32 3/8
15 3/4
400
36 5/8
18 1/8
460
40 3/4
1035
18 3/4
476
41 3/4
1060
21 3/4
552
47
1194
22 1/4
565
48
1219
24 3/4
629
52 1/8
1324
27 3/4
705
57 3/8
1457
28 1/4
718
58 3/8
1483
30 3/4
781
62 1/2
1588
33 3/4
857
67 3/4
1721
36 3/4
933
73
1854
39 3/4
1010
78 1/8
1984
41 1/8
1045
82 3/8
2092
45 3/4
1162
88 1/2
2248
48 1/8
1222
92 3/4
2356
51 3/4
1314
98 7/8
2511
Proper assembly of air cooled chimney parts results in an overlap of chimney joints
of 1-1/4 in. (32 mm). Effective length is built into this table.
16
Heat & Glo LifeStyles Collection • Montana US-CAN • 4039-156 Rev C • 11/07
SL1106
SL1112
SL1118
mm
SL406
SL412
SL418
454
-
-
-
559
1
-
-
664
2
-
-
692
-
1
-
797
1
1
-
822
-
-
1
930
-
2
-
1
2
-
-
1
1
-
-
2
-
-
-
1
-
-
-
1
-
-
-
-
1
-
-
-
1
-
-
-
1
-
-
-
1
-
-
-
-
-
1
-
-
-
-
-
Measure how far the chimney needs to be shifted to enable
it to avoid the overhead obstacle. See Figure 5.1. Use
dimension "A" to determine chimney section required to
achieve the needed shift.
After determining the offset dimension, refer to Table 5.2
and fi nd the "A" dimension closest to but not less than the
distance of shift needed for your installation.
The "B" dimension that coincides with the "A" dimension
represents the required vertical clearance that is needed
to complete the offset and return.
Read across the chart and fi nd the number of chimney
sections required and the model number of those particular
chimney parts.
Whenever the chimney penetrates a fl oor/ceiling, a ceiling
fi restop must be installed.
The effective height of the fi replace assembly is measured
from the base of the fi replace to the top of the starter collar.
See Dimensions in Section 12.
SL1136
SL1148
SL436
SL448
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Figure 5.1
1
-
1
-
Example: Your "A" dimension from Figure 5.3 is
1
-
14 1/2 in. (368 mm). Using Table 5.2 the dimension
closest to, but not less than 14 1/2 in. (368 mm) is
-
1
15 3/4 in. (400 mm) using a 30° offset/return. It is
-
1
then determined from the table that you would need
-
1
36 5/8 in. (930 mm) (Dimension "B") between the
-
1
offset and return. The chimney components that best
2
-
fi t your application are two SL1112s or SL412s.
2
-
1
1
1
1
-
2
A
B
1-1/4 in. (32 mm)
OVERLAP
Chimney Offset/Return

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Montana-42

Table of Contents