Before Installation - Daikin FXLQ12MVJU Installation Manual

Vrv system inverter air conditioners
Hide thumbs Also See for FXLQ12MVJU:
Table of Contents

Advertisement

CAUTION
• While following the instructions in this installation man-
ual, insulate piping in order to prevent condensation.
Improper piping insulation may result in water leakage and
property damage.
• Do not touch the heat exchanger fins.
Improper handling may result in injury.
• Be very careful about product transportation.
Some products use PP bands for packaging. Do not use any
PP bands for a means of transportation. It is dangerous.
• Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden
parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that
children will not play with them. If children play with a plastic
bag which was not torn apart, they face the risk of suffoca-
tion.
• Do not turn off the power immediately after stopping
operation.
Always wait at least five minutes before turning off the power.
Otherwise, water leakage and trouble may occur.
NOTE
• Install the indoor and outdoor units, power supply wir-
ing and connecting wires at least 3.5ft. away from televi-
sions or radios in order to prevent image interference or
noise.
(Depending on the radio waves, a distance of 3.5ft. may not
be sufficient enough to eliminate the noise.)
• Remote controller (wireless kit) transmitting distance
can result shorter than expected in rooms with elec-
tronic fluorescent lamps. (inverter or rapid start types)
Install the indoor unit as far away from fluorescent lamps as
possible.
• This unit is a class A product.
In a domestic environment this product may cause radio
interference in which case the user may be required to take
adequate measures.
• Dismantling of the unit, treatment of the refrigerant, oil
and eventual other parts, should be done in accordance
with the relevant local and national regulations.
2.

BEFORE INSTALLATION

• When moving the unit while removing it from the packing
case, be sure to lift it without exerting any pressure on
other parts, especially, the refrigerant piping, drain pip-
ing, and other resin parts.
• Be sure to check the type of R410A refrigerant to be used
before installing the unit. (Using an incorrect refrigerant will
prevent normal operation of the unit.)
• The accessories needed for installation must be retained in
your custody until the installation work is completed. Do not
discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until reach-
ing the installation site. Where unpacking is unavoidable, use
a sling of soft material or protective plates together with a
rope when lifting, to avoid damage or scratches to the unit.
• For the installation of an outdoor unit, refer to the installation
manual attached to the outdoor unit.
• Do not install or operate the unit in rooms mentioned below.
• Laden with mineral oil, or filled with oil vapor or spray
like in kitchens. (Plastic parts may deteriorate which
could eventually cause the unit to fall out of place, or
could lead to leaks.)
• Where corrosive gas like sulfurous gas exists. (Cop-
per tubing and brazed spots may corrode which could
eventually lead to refrigerant leaks.)
• Where exposed to flammable gases and where vola-
tile liquids like thinner or gasoline is used. (Gas in the
vicinity of the unit could ignite.)
• Where machines can generate electromagnetic
waves. (Control system may malfunction.)
• Where the air contains high levels of salt such as that
near the ocean and where voltage fluctuates greatly
such as that in factories.
Also in vehicles or vessels.
• This unit, both indoor and outdoor, is suitable for installation in a
commercial and light industrial environment.
If installed as a household appliance it could cause electro-
magnetic interference.
NOTE
• Be sure to read this manual before installing the indoor unit.
• Entrust installation to the place of purchase or an authorized
serviceman. Improper installation could lead to leaks and, in
worse cases, electric shock of fire.
• Use only parts provided with the unit or parts satisfying
required specifications. Unspecified parts could cause the
unit to fall out of place, or could lead to leaks and, in worse
cases, electric shock or fire.
2-1
ACCESSORIES
Check the following accessories are included with your
unit.
Name
Drain hose
Quantity
1 set
Hose × 1
Metal clamp × 1
Shape
Name
Sealing pad
Quantity
1 pc.
Shape
Name
Leveling screw
Quantity
4 pcs.
Shape
2-2
OPTIONAL ACCESSORIES
Table 1
Remote controller
Wired type
Insulation for
fitting
1 each
(3) For gas pipe
(4) For liquid pipe
Clamp
8 pcs.
[Other]
• Operation manual
• Installation manual
BRC1C71
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fxnq18mvjuFxlq18mvjuFxlq24mvjuFxnq12mvjuFxnq24mvju

Table of Contents