FOR THE FOLLOWING ITEMS, TAKE SPECIAL
CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checked
Are the indoor and
outdoor unit fixed firmly?
Is the gas leak test
finished?
Is the unit fully insulated?
Does drainage flow
smoothly?
Does the power supply
voltage correspond to
that shown on the name
plate?
Are wiring and piping
correct?
Is the unit safely
grounded?
Is wiring size according
to specifications?
Is something blocking
the air outlet or inlet of
either the indoor or
outdoor units?
Are refrigerant piping
length and additional
refrigerant charge noted
down?
b. Items to be checked at time of delivery
Also review the "SAFETY CONSIDERATIONS"
Items to be checked
Did you explain about operations while showing the
operation manual to your customer?
Did you hand the operation manual over to your cus-
tomer?
c. Points for explanation about operations
The items with
WARNING and
the operation manual are the items pertaining to possibility
for bodily injury and material damage in addition to the gen-
eral usage of the product. Accordingly, it is necessary that
you make a full explanation about the described contents
and also ask your customers to read the operation manual.
2-3
NOTE TO THE INSTALLER
Be sure to instruct customers how to properly operate the
unit (especially cleaning filters, operating different functions,
and adjusting the temperature) by having them carry out
operations themselves while looking at the manual.
3
If not properly done, what
is likely to occur
The units may drop,
vibrate or make noise.
It may result in insuffcient
cooling.
Condensate water may
drip.
Condensate water may
drip.
The unit may malfunction
or the components burn
out.
The unit may malfunction
or the components burn
out.
It may be dangerous at
electric leakage.
The unit may malfunction
or the components burn
out.
It may result in
insufficient cooling.
The refrigerant charge in
the system is not clear.
CAUTION marks in
3.

SELECTING INSTALLATION SITE

(1) Select an installation site where the following condi-
tions are satisfied and that meets with your customer's
approval.
• Where the floor is strong enough to bear the indoor unit
weight.
Check
• Where the floor is not significantly inclined.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where sufficient clearance for installation and mainte-
nance can be ensured.
• Where optimum air distribution can be ensured.
• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is possi-
ble within the allowable limit. (Refer to the installation
manual of the outdoor unit.)
CAUTION
• Install the indoor and outdoor units, power supply wiring
and connecting wires at least 3.5 ft. away from televisions
or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.5 ft. may
not be enough to eliminate the noise.)