Connection Of The Safety Valve Discharge - Liebert CBH 017 Service Manual

High performance air cooled chiller
Table of Contents

Advertisement

Tab. a -- Ethylene glycol to be added to water
(% in weight of total mixture)
Ethylene glycol
0
(% in weight)
Freezing tempera-
0
---4.4
(*)
ture, ûC
Mixture density at
---
1.017
(*)
20ûC
, kg/l
(*) Values are for Shell antifreeze 402. For different brands, check
manufacturer's data.
For the chiller internal water volume refer to Tab. 1. If the optional
buffer tank is installed on the machine, add the tank hydraulic
volume.
Fig. a -- Ideal chilled water circuit
10a
10b
10c
Fig. b -- Inertia tank sizing
The total optimum hydraulic volume of the system where the Matrix S chiller is installed can be calculated by the
following formula:
43 x Rt
V =
Xd
where:
---
V=minimum required total water volume expressed in litres
---
Rt=refrigeration capacity expressed in kW
---
Xd=differential band set on the control and expressed in degrees centigrade
Please note that the sum of the hydraulic volume of the Matrix S chiller (Vm) plus the volume of the hydraulic circuit
connected to it (Vpc) must be greater than, or equal to the minimum required total water volume (V). If this condi-
tion is not satisfied, it is necessary to install an inertia tank (Vpt, as indicated in the Fig. a) with a volume at least
equal to the following value: Vpt=V ---Vm ---Vpc
10
20
30
40
---9.9
---16.6
---25.2
1.033
1.048
1.064
disconnect af-
ter charge
10e
10d
12
ALWAYS CHARGE THE HYDRAULIC CIRCUIT WITH THE RE-
QUIRED GLYCOL % NECESSARY FOR THE MINIMUM AMBI-
ENT TEMPERATURE AT THE INSTALLATION SITE. FAILING
TO COMPLY WITH THIS INSTRUCTION SHALL INVALIDATE
50
THE UNIT WARRANTY.
---37.2
3.2 --- Connection of the safety valve
1.080
Safety valves are installed on the high pressure side of the refrig-
eration circuit: the discharge of these valves must be conveyed
outside through a suitable pipe, having a diameter of at least that
of the valve outlet, without burdening the valve body. Convey the
discharge to areas where the jet cannot harm people and the
surrounding environment.
1
6
3
4
7
T
5
Vpt
Tank
USER
9
1
3
discharge
2
5
CHILLER
5
1
11
3
4
1
8
T
9