Low-Voltage Detection Or Over-Voltage Detection - Daikin FTX20JV1B Service Manual

Inverter pair wall mounted type j-series
Hide thumbs Also See for FTX20JV1B:
Table of Contents

Advertisement

Troubleshooting
4.7

Low-voltage Detection or Over-voltage Detection

U2
Error Code
Method of Error
Low-voltage detection:
An abnormal voltage drop is detected by the DC voltage detection circuit.
Detection
Over-voltage detection:
An abnormal voltage rise is detected by the over-voltage detection circuit.
Error Decision
Low-voltage detection:
Conditions
Over-voltage detection:
Supposed
Causes
59
The voltage detected by the DC voltage detection circuit is below 180 V.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer.
The compressor stops if the error occurs, and restarts automatically after 3-minute standby.
Power supply voltage is not as specified.
Defective DC voltage detection circuit
Defective over-voltage detection circuit
Defective PAM control part
Disconnection of compressor harness
Short circuit inside the fan motor winding
Noise
Momentary fall of voltage
Momentary power failure
Defective outdoor unit PCB
SiBE041010EA
Service Diagnosis