Thermistor Or Related Abnormality (Outdoor Unit) - Daikin FTX20JV1B Service Manual

Inverter pair wall mounted type j-series
Hide thumbs Also See for FTX20JV1B:
Table of Contents

Advertisement

SiBE041010EA

4.21 Thermistor or Related Abnormality (Outdoor Unit)

H9 , J3 , J6 , P4
Error Code
Method of Error
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Detection
Error Decision
Conditions
Supposed
Causes
In case of " P4 "
Troubleshooting
Replace the outdoor unit PCB.
P4
Service Diagnosis
The thermistor input voltage is above 4.96 V or below 0.04 V with the power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Disconnection of the connector for the thermistor
Thermistor corresponding to the error code is defective
Defective heat exchanger thermistor in the case of J3 error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
: Radiation fin thermistor
Troubleshooting
78

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents