12. Operation Control

12.1 Basic Function

12.1.1 Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the air conditioner settings and the operation environment.
The final shifted value will be used as internal setting temperature and it is updated continuously whenever the
electrical power is supplied to the unit.
12.1.2 Cooling Operation
12.1.2.1
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point +0.5K.
12.1.3 Soft Dry Operation
12.1.3.1
Thermostat control
• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5℃
• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature >
Compressor OFF point +0.5K.
Remote Control Setting Temp. (16℃~30℃)
Auto operation Mode Shifting
Setting Temperature Limit Checking (Min.:16℃~Max.:30℃)
Powerful Temperature Shifting
Fan speed Shifting
Dry mode Shifting
Cooling/Heating Shifting
Setting Temperature Limit Checking(Min: 16℃; Max.: 33℃)
Internal Setting Temperature