Burner Assembly And Mounting - Brant Radiant Heaters HLV Series Instructions For Intallation

Gas-fired infrared vacuum system tube heater
Table of Contents

Advertisement

3.0
Installation

Burner Assembly and Mounting

Burner Assembly and Mounting
Conditions such as wind drafts or other variables can cause movement of the heater and
may require it to be rigidly mounted. Avoid excessive movement and/or vibration of the
gas connection by rigidly mounting the burner control box. All remaining hanging points
should use chains to allow for expansion.
The heater must be independently supported and in no case shall the gas or electrical supply support
the weight of the heater.
Determine the mounting chain locations for hanging the burner control box.
1
Fasten beam clamp, screw hook or other type of suspension anchor to hanging point.
2
Attach S-Hook and #1 double loop chain (P/N: THCS) to anchor. Check that it is securely
3
connected.
Attach chain assemblies and S-Hooks to mounting brackets on the burner control box. Adjust chain
4
lengths until level and in straight alignment with radiant tubes (Figure 3.16).
Figure 3.16 •
Burner Control Box Assembly
Burner box
mounting
bracket
8.1"
12"
Figure 3.17 •
Burner Control Box
3.5"
5.5"
WARNING
!
Side View
Burner tube is in straight
alignment with 10 ft. Primary
Combustion Chamber
Burner Sight Glass
(bottom side of the tube)
16"
End View
18"
5"
8.1"
3"
30
HLV
Series

Advertisement

Table of Contents
loading

Table of Contents