Recommended Mounting Heights And Coverages; Application Guidelines - Brant Radiant Heaters QTS Series Manual

Gas-fired infrared quad tube heater
Table of Contents

Advertisement

QTS
Series
3.0
Chart 3.1

Recommended Mounting Heights and Coverages

Model No.
QTS-40 [N,P]
QTS-60 [N,P]
QTS-80 [N,P]
NOTE: This chart is provided as a guideline. Actual conditions may dictate variation from this data.
*Factory recommended mounting heights and approximate coverages are listed as a guideline for
designing for total building heat. However, certain applications such as spot heating, freeze protection
and outdoor heating generally require additional heat per square foot to comfortably heat these areas.
Clearances to Combustibles must always be maintained (Chart 2.1; Page 9).
Figure 3.1

Application Guidelines

DIM A - Distance from heater to wall = 8 ft. to 20 ft.
DIM B - Distance between heaters = 12 ft. to 28 ft.
NOTE: Dimensions A & B are based upon heaters hung at the factory recommended mounting height.
Installation
Recommended Mounting Heights and Coverages
Input
Recommended
BTU/h
Mounting Height (ft.)*
40,000
60,000
80,000
Dim. B
Approximate Coverage Area
8 to 10
8 to 12
10 to 14
Dim. A
Dim. A
11
Application Guidelines
(LxW)*
25 x 35
30 x 40
35 x 45