System Start-Up Prechecks; Damper Adjustment - Brant Radiant Heaters HLV Series Instructions For Intallation

Gas-fired infrared vacuum system tube heater
Table of Contents

Advertisement

4.0
Operation
System Start-Up and Damper Adjustment

System Start-Up Prechecks

• Confirm all gas piping, electrical wiring, etc. are properly installed.
• Preset the primary and secondary damper(s) to half-open.
• If applicable, unassisted combustion air ducts must be installed before start-up.
• If applicable, fan assisted outside combustion air ducts must not be connected to burner control box
upon initial start-up.

Damper Adjustment

The system must run for 20 minutes in high fire mode before setting the dampers. Confirm all
1
operational indicator lights (located on the burner control box) are on.
All system dampers are preset to half-open. If a burner fails to stay lit or does not light, the damper
2
serving that burner must be adjusted until the burner is continually lit throughout the initial 20 minute
start-up.
Using a manometer with an adequate range, measure the vacuum pressure (Figure 4.2) at the
3
burner furthest from the vacuum pump. Adjust the primary damper at the pump until the manometer
reaches the specified reading shown in Chart 4.2.
NOTE: If proper box static pressure cannot be achieved, it may be necessary to remove one, two or
all three baffle sections (P. 27). Consult factory following basic troubleshooting (i.e. proper pump
rotation, check for blockages, baffle installed correctly, control box covers are secured, etc.).
Figure 4.2 •
Burner Control Box Vacuum Port
NOTE: Remove the plug on
vacuum port to measure box
pressure. Ensure burner box
lid is tightened securely.
If secondary dampers are installed in the system, connect manometer to each applicable burner
4
and set applicable secondary damper to the specified reading (Chart 4.2).
Once each damper has been adjusted, burner pressures must be checked to confirm initial
5
setpoints did not change. Readjust dampers as necessary in the same order. Lock dampers in place.
If fan assisted outside air ducts are used, connect to control box after initial start-up is complete;
6
Adjust supply dampers (supplied with powered air inlet P/N: V-PAI - sold separately) until the
required pressures are achieved.
Chart 4.2 •
Burner Box Pressure Setpoints
Burner Box Input (BTU/H)
40,000 to 60,000
75,000 to 110,000
120,000 to 180,000
200,000
The system must operate in high fire for 20 minutes before adjusting the dampers.
Each system damper must be adjusted to the box pressure setpoints listed above.
Box Pressure (inches W.C.)
-0.51 +/- .01
-0.19 +/- .01
-0.22 +/- .01
-0.19 +/- .01
Vacuum Port
44
HLV
Series