Pilot Burner Replacement - IDEAL classic HE15P Installation And Servicing Manual

Classic he p series
Hide thumbs Also See for classic HE15P:
Table of Contents

Advertisement

65 LIMIT THERMOSTAT REPLACEMENT
1. Refer to Frame 61.
2. Remove the limit thermostat assembly from the
boiler flow pipe.
3. Disconnect the electrical connectors
4. Clip new thermostat onto flow pipe
5. Reassemble in reverse order.
NOTE. UNDER NO CIRCUMSTANCES REFIT THE
LIMIT THERMOSTAT ONTO THE RETURN PIPE
66 FLUE PROTECTION THERMOSTAT REPLACEMENT
1. Refer to Frame 61.
2. Pull off the two electrical connections.
3. Remove the two nuts retaining the flue protection
thermostat.
4. Replace the thermostat and re-assemble in reverse
order

67 PILOT BURNER REPLACEMENT

1. Refer to Frame 61.
2. Remove the burner and air box assembly. Refer to Frame
54.
3. Remove the electrode retaining nut and remove the pilot
shield and electrode.
4. Unscrew the central pilot fixing screw and lift the pilot clear
of the pilot injector. The pilot injector may now be unscrewed
if required.
5. Replace the pilot burner (injector if necessary) and retain
with the M4 screw previously removed. Ensure the copper
sealing washer is replaced when refitting the pilot injector.
classic HE P -
Installation & Servicing
SERVICING
Return pipe
2
6. Replace the electrode and pilot shield, retaining
both with the electrode nut. Check the spark gap.
7. Reassemble in reverse order.
8. Check the operation of the boiler.
9. The pilot is factory set to maximum and no further
adjustment is possible. Ensure there is an inlet
pressure of 37 mbar available. Also check burner
ignition and cross-lighting.
Flow pipe
2
3
3
37