How to Cope with Test Run Abnormality

The phenomena from main component failure
Component
Phenomenon
Not operating
Compressor
Stop during running
Abnormal noise
during running
High pressure error
Outdoor
at cooling
fan
Heating failure, fre-
quent defrosting
No operating sound
at applying power
Outdoor
Heating failure,
EEV
frozen outdoor heat
exchanger part
Low pressure error
or discharge temper-
ature error
When system fault occurs, the error code is displayed at indoor unit display or remote control display,
the trouble shooting guide is in the service manual
Cause
Motor insulation broken
Check resistance between terminals and
chassis
Strainer clogged
Change strainer
Oil leakage
Check oil amount after opening oil port
Motor insulation failure
Check resistance between terminals and
chassis
R-S-T misconnection
Check compressor R-S-T connection
Motor failure,
Check the outdoor fan operation after being
bad ventilation around
turned the outdoor units off for some time.
outdoor heat exchanger
Remove obstacles around the outdoor units
Bad connector contact
Check connector
Coil failure
Check resistance between terminals
EEV clogged
Service necessary
EEV clogged
Service necessary
Check method and Trouble shooting