LG ARUN115DT2 Installation Manual page 37

Arun/aruv series
Hide thumbs Also See for ARUN115DT2:
Table of Contents

Advertisement

Available languages

Available languages

N The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe.
Product Charge(kg(lb))
A
Additional charge (kg(lb))
B
=
Total liquid pipe (m(ft.)): Ø22.2mm(7/8inch)
+
Total liquid pipe (m(ft.)): Ø19.05mm(3/4inch)
+
Total liquid pipe (m(ft.)): Ø15.88mm(5/8inch)
+
Total liquid pipe (m(ft.)): Ø12.7mm(1/2inch)
+
Total liquid pipe (m(ft.)): Ø9.52mm(3/8inch)
+
Total liquid pipe (m(ft.)): Ø6.35mm(1/4inch)
CF(kg(lb))
+
(Correction Factor)
Total amount(kg(lb))
CAUTION
If a negative result is obtained from
the calculation, no refrigerant needs
to be added.
• 460V
HP
8
8
Product Charge kg(lbs)
(17.6)
-1
CF
kg(lbs)
(-2.2)
• 208/230V
HP
8
Product Charge
kg(lbs)
8(17.6)
CF
kg(lbs)
-1(-2.2)
WARNING
Regulation for refrigerant leakage
: the amount of refrigerant leakage should satisfy the following equation for human safety.
Total amount of refrigerant in the system
Volume of the room at which Indoor Unit of the least capacity is installed
❐ If the above equation can not be satisfied, then follow the following steps.
- Selection of air conditioning system: select one of the next
1. Installation of effective opening part
2. Reconfirmation of Outdoor Unit capacity and piping length
3. Reduction of the amount of refrigerant
4. Installation of 2 or more security device (alarm for gas leakage)
- Change Indoor Unit type
: installation position should be over 2m(6.6ft) from the floor (Wall mounted type ¡ Cassette type)
- Adoption of ventilation system
: choose ordinary ventilation system or building ventilation system
- Limitation in piping work
: Prepare for earthquake and thermal stress
WARNING
Refer to model information since the CF Value of correction factor differs depending on model.
x 0.354(kg/m) ¡ 0.237 lb/ft
x 0.266(kg/m) ¡ 0.178 lb/ft
x 0.173(kg/m) ¡ 0.116 lb/ft
x 0.118(kg/m) ¡ 0.079 lb/ft
x 0.061(kg/m) ¡ 0.041 lb/ft
x 0.022(kg/m) ¡ 0.015 lb/ft
=
+
A
B
10
12
14
16
8
8
8
8
(17.6)
(17.6)
(17.6)
(17.6)
0
1
2
3
(0)
(2.2)
(4.4)
(6.6)
10
12
8(17.6)
8(17.6)
0(0)
1(2.2)
Refrigerant piping installation
Ex
10HP
Outdoor Unit
Indoor Unit
A : ø9.52(3/8), 40m(131ft)
B : ø9.52(3/8), 20m(65.6ft)
C : ø9.52(3/8), 20m65.6ft)
A
C
c
d
3
B
4
B
B
a
B
1
Additional charge = A*0.041 + B*0.041 + C*0.041
+(a+b+c+d+e)*0.015 + CF
= 40*0.041+20*0.041+65.6*0.041
+ (32.8*5)*0.015 + (0)(CF)
= 7.61(lb)
18
20
22
24
8+8
8+8
8+8
8+8
(17.6+17.6)
(17.6+17.6)
(17.6+17.6)
(17.6+17.6)
-1
0
1
2
(-2.2)
(0)
(2.2)
(4.4)
16
18
8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6) 8+8(17.6+17.6)
-2(-4.4)
-1(-2.2)
0.44 (kg / m
a : ø6.35(1/4), 10m(32.8ft)
b : ø6.35(1/4), 10m(32.8ft)
c : ø6.35(1/4), 10m(32.8ft)
d : ø6.35(1/4), 10m(32.8ft)
e : ø6.35(1/4), 10m(32.8ft)
X
e
5
B
b
B
2
26
28
30
8+8
8+8
8+8
(17.6+17.6)
(17.6+17.6)
(17.6+17.6)
(17.6+17.6)
3
4
5
(6.6)
(8.8)
(11.0)
(13.2)
20
22
24
0(0)
1(2.2)
2(4.4)
3
3
)(0. 028(lb/ft
))
Installation Manual 37