LG ARUN115DT2 Installation Manual page 32

Arun/aruv series
Hide thumbs Also See for ARUN115DT2:
Table of Contents

Advertisement

Available languages

Available languages

Refrigerant piping installation
➲ Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit total capacity
[kW(Btu/h)]
<22.4(76,400)
< 33(112,600)
< 47(160,400)
< 71(242,300)
< 104(354,900)
➲ Total pipe length = A+B+C+a+b+c+d+e ≤ 1,000m(3,281 ft)
Longest pipe length
L
A+B+b ≤ 150m(492ft)
Longest pipe length after 1st branch
l
B+b ≤ 40m(131ft)
Difference in height(Outdoor Unit ↔ Indoor Unit)
H
H ≤ 100m(328ft)
Difference in height (Indoor Unit ↔ Indoor Unit)
h
h ≤ 15m(49ft)
Difference in height (Outdoor Unit ↔ Outdoor Unit)
h1
h1 ≤ 5m(16ft)
• * : Assume equivalent pipe length of Y branch to be 0.5m(1.6ft), that of header to be 1m(3.3ft), calculation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
It is recommended that difference of piping length for pipes connected to the Indoor Unit is
minimized. Performance difference between Indoor Units may occur.
Upward Outdoor Unit
total capacity [HP]
8
10
12~16
18~22
24
26~32
32
Outdoor Unit
Liquid pipe
[mm(inch)]
Ø15.88(5/8)
Ø19.05(3/4)
* Equivalent pipe length
A+B+b ≤ 175m(574ft)
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø34.9(1-3/8)
Ø19.05(3/4)
Ø34.9(1-3/8)
Gas pipe
[mm(inch)]
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)
Ø28.58(1-1/8 )
Ø34.9(1-3/8)
Upward Outdoor Unit
total capacity [HP]
20, 22, 24
26, 28, 30, 32
Upward Outdoor Unit
total capacity [HP]
8
10
12, 14, 16
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø15.88(5/8) Ø28.58)(1-1/8)
Ø19.05(3/4)
Ø34.9(1-3/8)
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents