Mitsubishi Mr.SLIM PUH18EK Technical & Service Manual page 27

Split-type, heat pump air conditioners
Table of Contents

Advertisement

Outdoor unit (PUH24EK)
OPERATING PROCEDURE
1. Electrical parts
(1) Remove top panel (3 screws in front, 2 screws in rear)
(2) Remove cover panel (1 screw).
The panel is anchored by clicks to the side panel.
Remove by pulling towards you.
(3) Remove cover panel (1 screw).
The panel is clasped on the right and left sides. After remov-
ing the screw, pull the panel down and remove it by pulling
towards you.
2. Fan motor
(1) Remove front panel (3 screws).
Open the panel to a 45 degree angle and lift to remove. The
panel is clasped at three points on the left side.
(2) Remove propeller (1 set nut).
(3) Remove fan motor (3 screws).
Remove lead connector.
NOTE : All panels are clasped, and should be
Photo 1
Photo 2
Compressor protector
Screws
Photo 3
Propeller
nut
Propeller fan
27
removed by shifting up and down.
PHOTOS
Screws
Panel cover
Run capacitor
52C relay
Terminal block
Motor support
Separator support place
High-pressure
switch
Valve bed
Crank case heater

Hide quick links: