PSA-RP·KA

INSTALLATION MANUAL

For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing
the air-conditioner unit.
INSTALLATIONSHANDBUCH
Aus Sicherheitsgründen und zur richtigen Anwendung vor Installation der Klimaanlage die vorliegende Bedie-
nungsanleitung und das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Avant d'installer le climatiseur, lire attentivement ce manuel, ainsi que le manuel d'installation de l'appareil
extérieur pour une utilisation sûre et correct.
INSTALLATIEHANDLEIDING
Lees deze handleiding en de installatiehandleiding van het buitenapparaat zorgvuldig door voordat u met het
installeren van de airconditioner begint.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de
aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, prima di installare il condizionatore d'aria leggere attentamente il presente manuale
ed il manuale d'installazione dell'unità esterna.
EΓXEIPIΔIO OΔHΓIΩN EΓKATAΣTAΣHΣ
Για σωστή και ασφαλή χρήση, διαβάστε προσεκτικά αυτό το εγχειρίδιο, καθώς και το εγχειρίδιο εγκατάστασης
της εξωτερικής μονάδας, πριν από την εγκατάσταση της μονάδας κλιματιστικού.
MANUAL DE INSTALAÇÃO
Para uma utilização segura e correcta, leia atentamente este manual e o manual de instalação da unidade
exterior antes de instalar o aparelho de ar condicionado.
INSTALLATIONSMANUAL
Læs af sikkerhedshensyn denne manual samt manualen til installation af udendørsenheden grundigt, før du
installerer klimaanlægget.
INSTALLATIONSMANUAL
Läs bruksanvisningen och utomhusenhetens installationshandbok noga innan luftkonditioneringen installeras så
att den används på ett säkert och korrekt sätt.
MONTAJ ELKİTABI
Emniyetli ve doğru kullanım için, klima cihazını monte etmeden önce bu kılavuzu ve iç ünite montaj kılavuzunu
tamamıyla okuyun.
FOR INSTALLER
FÜR INSTALLATEURE
POUR L'INSTALLATEUR
VOOR DE INSTALLATEUR
PARA EL INSTALADOR
PER L'INSTALLATORE
ΓΙΑ ΑΥΤΟΝ ΠΟΥ ΚΑΝΕΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ
PARA O INSTALADOR
TIL INSTALLATØREN
FÖR INSTALLATÖREN
MONTÖR İÇİN
English
Deutsch
Français
Nederlands
Español
Italiano
Eλληνικά
Português
Dansk
Svenska
Türkçe

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Mr.SLIM PSA-RP-KA

  • Page 1: Installation Manual

    Air-Conditioners PSA-RP·KA INSTALLATION MANUAL FOR INSTALLER English For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH FÜR INSTALLATEURE Deutsch Aus Sicherheitsgründen und zur richtigen Anwendung vor Installation der Klimaanlage die vorliegende Bedie- nungsanleitung und das Installationshandbuch gründlich durchlesen.
  • Page 2: Table Of Contents

    • The terminal block cover panel of the unit must be firmly attached. in the outdoor unit installation manual. • Use only accessories authorized by Mitsubishi Electric and ask a dealer or • The unit must be installed according to the instructions in order to minimize an authorized technician to install them.
  • Page 3: Installation Location

    2. Installation location 2.1. Outline dimensions (Indoor unit) (Fig. 2-1) Select a proper position allowing the following clearances for installation and main- tenance. (mm) Models 71,100,125,140 1900 Min. 100 Min. 1000 Min. 5 * Do not place any objects within 1000 mm of the air outlet. Warning: Mount the indoor unit on a ceiling strong enough to withstand the weight of the unit.
  • Page 4: Installing The Refrigerant Piping

    3. Installing the indoor unit (mm) 3.3. Mounting the tip-over prevention bracket (Fig. 3-3) • Select one of the following mounting methods, depending on the height of the frieze inside the wall above the floor. • In the case of a light steel bed, a frieze is generally not used, so the bracket should be mounted to one of the supports or pillars (obtain the screws locally).
  • Page 5: Tions

    4. Installing the refrigerant piping 4.2. Indoor unit (Fig. 4-1) 45° ±2° • When commercially available copper pipes are used, wrap liquid and gas pipes with commercially available insulation materials (heat-resistant to 100 °C or more, thickness of 12 mm or more). •...
  • Page 6: Drainage Piping Work

    4. Installing the refrigerant piping Refrigerant piping connection (Fig. 4-4) 1. Remove the screw from the air intake grill handle and then remove the air intake grill by pulling it up and forward. 2. Remove the tapping screw that holds the pipe support in place and then remove the pipe support.
  • Page 7: Electrical Work

    6. Electrical work 6.1. Electric wiring (Fig. 6-1) 1. Remove the tapping screws a and then remove the electrical equipment cover 2. Connect the electric wires securely to the corresponding terminals. 3. Fasten the wires d with the bands c. •...
  • Page 8 6. Electrical work 6.1.2. Separate indoor unit/outdoor unit power supplies (For PUHZ application only) The following connection patterns are available. The outdoor unit power supply patterns vary on models. 1:1 System A Outdoor unit power supply * The optional wiring replacement kit is required. B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit...
  • Page 9: Function Settings

    6. Electrical work 6.2. Function settings 6.2.1. Function setting on the unit (Fig. 6-2) Mode number Changing the power voltage setting Setting number • Be sure to change the power voltage setting depending on the voltage used. Refrigerant address 1 Go to the function setting mode. Unit number Switch OFF the remote controller.
  • Page 10: Test Run

    7. Test run 7.1. Before test run ► After completing installation and the wiring and piping of the indoor and ► Do not carry out this test on the control wiring (low voltage circuit) termi- outdoor units, check for refrigerant leakage, looseness in the power supply nals.
  • Page 11 7. Test run [Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.) Check code Symptom Remark Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Compressor overcurrent interruption U3, U4 Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharging temperature/49C worked/insufficient refrigerant U1, Ud Abnormal high pressure (63H worked)/Overheating safeguard operation...
  • Page 12: Easy Maintenance Function

    8. Easy maintenance function Display example (Comp discharge temperature 64 °C) By using the maintenance mode, you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units. This function can be used whether the air conditioner is operating or not.
  • Page 13 This product is designed and intended for use in the residential, commercial and light-industrial environment. • The product at hand is Low Voltage Directive 73/23/EEC • based on the following Electromagnetic Compatibility Directive 89/ EU regulations: 336/EEC • Machinery Directive 2006/42/EC •...