Figure 4: Plumbing with isolation valve with strainer to be fitted to return pipe

3.6.1 Buffer tank

The heat pump uses reverse cycle
defrost
in
order
evaporator,
which
automatically
cold/moist
weather
Therefore, it is necessary to connect a
buffer tank in series with the heat
pump,
as
shown
schematic diagrams (Appendix B). The
Dimplex A-Class cylinder range come
with an integrated buffer tank, which:
Provides sufficient energy for the
unit to carry out successful defrost.
Increases compressor life due to the
extension of minimum starts
It is recommended that a buffer with a
heating element is used as it may be
required
if
initial
commissioning are carried out in cold
weather.
to
defrost
will
happen
when
required
conditions.
in
the
hydraulic
start-up
3.7 Electrical connections -
Preparation
the
Ensure the incoming power supply
and
in
suitably rated.
Ensure that the regulations specified
by the local electricity supplier have
been adhered to.
The supply cable must be sized to
meet the requirements of national
wiring
carrying capacity and disconnection,
a minimum cross sectional area of
6mm² steel wire armoured (SWA)
cable is recommended.
The required controller cable is a
shielded MODBUS cable RS485, for
example a 4 core 1mm² 24 AWG
and
(Nominal impedance 120Ω) Foil and
Braid, which can be purchased from
Dimplex as an accessory.
9
the
distribution
regulations
board
are
for
current