Switch-mode battery charger (microprocessor system)
Hide thumbs Also See for INVERTEK:
Table of Contents

Advertisement

1. Connect the positive battery on terminal marker +BAT 1 and open the entry of the
upper case to tighten it with screws.
2. Connect the negative battery cable to terminal marker –BAT and open the entry of the
upper case to tighten it with screws.
3. Do the same for batteries number 2 and 3 for +BTA 2 and +BTA 3. For a 3 outputs
charger, refer to the table below to choose conductor section.
B T S1
BT S 2
B T S3
+B A T 3
+B A T 2
+B A T 1
-B A T
Figure A: Batteries terminals and BTS terminals
Battery fuse board:
Model No.
FUSE Atofuse (car)
Model No.
FUSE Atofuse (car)
WARNING: Check carefully the tightness of the battery connections to the charger (risk
if not properly tightened). Rich Electric will not take charge of damage caused by a
bad tightness of connections.
Don't connect a charge distributor on an Invertek charger, 1 or 3 outputs.
4. Put the AC power cord in the rear panel. The charger operates on sector 90V to 250
VAC - 50/60 Hz.
5. Conductor section according to charge current cables length is as follows.
Length
5m
Current
30A
6 mm
40A
10 mm
50A
16 mm
60A
25 mm
Main fuse board:
Model No.
Temporized glass fuse 6.3x32mm
12V/20A
1 x 25A
24V/15A
1 x 15A
10m
2
2
10
mm
2
2
16
mm
2
2
25
mm
2
2
25
mm
+ B A T3
+B A T2
+B A T1
12V/40A
12V/60A
2 x 25A
2 x 30A
24V/30A
24V/50A
2 x 15A
2 x 30A
Sector flex section (5m)
15m
220V
2
16
mm
1.5 mm
2
25
mm
1.5 mm
2
35
mm
1.5 mm
2
35
mm
1.5 mm
12V/20A, 12V/40A, 12V/40A,
24V/15A, 24V/30A, 24V/50A
16A
6
B T S1 B T S 2 B T S3
-B A T
Puissance
110V
2
2
2.5 mm
2
2
1.5 mm
2
2
2.5 mm
2
2
2.5 mm
(W)
750