Samsung MH020FPEA Service Manual page 180

Multi air conditioner
Hide thumbs Also See for MH020FPEA:
Table of Contents

Advertisement

12-3-2 Checking Outdoor Controller
1. Making sure the wire connections.
2. Checking AC line
1) Checking FUSE
2) Checking resistance between 'L wire (BRN)' and 'DB01 Live
side' normal value : 190 - 210Ω
If value is ∞ then check R001.
3) Checking resistance between 'N wire (SKYBLU)' and 'DB01 Neutral side'
normal value : 0 - 0.1Ω
3. Checking ON/OFF pattern of LED1(Red), LED2(Green), LED3(Yellow)
Apply the power then ALL LEDs are on for about 1 second. then changed to as follow.
I LED1 (Red) : ALWAYS ON
I LED2 (Green) : Blinking 4 times a second
(This means communication between 2 micoms IC01 and IC50 is normal)
I LED3 (Yellow) : OFF
G In case of another pattern inverter micom detects some hardware trouble or abnormal condition.
Yellow
Green
Status indication
OFF
OFF
ON
ON
OFF
Blink
Hardware trouble
OFF
OFF
Blink
Blink
ON
Blink
ON
ON
ON
OFF
Abnormal condition
OFF
OFF
OFF
Blink
ON
OFF
OFF
ON
Blink
ON
Samsung Electronics
Red
Description
OFF
Power OFF / No power (SMPS error)
ON
Power on reset ( 1~2 seconds )
ON
Normal operation
Communication Error between
ON
Main micom and inverter micom
ON
Current sensor error
Blink
DC-LINK sensor error
AC-Line zero crossing error
Blink
DC LINK capacitor discharged.(Max 20sec.)
Blink
Option error (EEPROM error)
Blink
Comp. peak current (Over Current)
OFF
Comp. starting error
ON
Comp. rotation error
Blink
DC-Link voltage error
OFF
Unit Over current protection
Live side
BD01
Note
If always in this pattern IC01(inverter micom)
has some trouble.
After power off this error will display until
Troubleshooting
Neutral side
12-7
12-7