Page 96
6.1.6 I/O store for a 115S-12 Expansion I/O module
0001 + Offset
DIO Outputs 1 - 8
0008 + Offset
10001 + Offset
DIO Inputs 1 - 8
10008 + Offset
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30001 + Offset
Inputs AIN 1 – AIN8
30008 + Offset
30017 + Offset
Modbus Error Counter for this 115S module
30018 + Offset
Modbus Last Error Code for this 115S module
30019 + Offset
Modbus Lost Link Counter for this 115S module
30020 + Offset
Module type (0x0201) = 513. / Error Status
40009 + Offset
Pulsed Output target 1 – 8 (1 register per output)
40016 + Offset
6.1.7 I/O store for a 115S-13 Expansion I/O module
0001 + Offset
DIO Outputs 1 - 8
0008 + Offset
10001 + Offset
DIO Inputs 1 - 8
10008 + Offset
10019 + Offset
Modbus Error indication for 115S module
10020 + Offset
Detected indication for this 115S module
30017 + Offset
Modbus Error Counter for this 115S module
30018 + Offset
Modbus Last Error Code for this 115S module
30019 + Offset
Modbus Lost Link Counter for this 115S module
30020 + Offset
Module type (0x0301) = 769. / Error Status
40001 + Offset
Analog Output 1 – 8
40008 + Offset
40009 + Offset
Pulsed Output target 1 – 8 (1 register per pulsed output)
40016 + Offset
Page 96
915U-2 Wireless I/O
User Manual