Elpro Technologies 905U-G User Manual

Wireless gateway
Table of Contents

Advertisement

Quick Links

User Manual

905U-G Wireless Gateway
ELPRO Technologies Pty Ltd, 9/12 Billabong Street, Stafford Q 4053, Australia.
Tel: +61 7 33524533 Fax: +61 7 33524577
Email: sales@elprotech.com
Web: www.elprotech.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 905U-G and is the answer not in the manual?

Questions and answers

Summary of Contents for Elpro Technologies 905U-G

  • Page 1: User Manual

    User Manual 905U-G Wireless Gateway ELPRO Technologies Pty Ltd, 9/12 Billabong Street, Stafford Q 4053, Australia. Tel: +61 7 33524533 Fax: +61 7 33524577 Email: sales@elprotech.com Web: www.elprotech.com...
  • Page 2 Important Notices Thank you for your selection of the 905G module. We trust it will give you many years of valuable service. ATTENTION! Incorrect termination of supply wires may cause internal damage and will void warranty. To ensure your 905G enjoys a long life, double check ALL your connections with the user’s manual before turning the power on.
  • Page 3: Fcc Notice

    905U-G Wireless Gateway User Manual FCC Notice: This user’s manual is for the ELPRO 905U-G radio telemetry module. This device complies with Part 15.247 of the FCC Rules. Operation is subject to the following two conditions: This device may not cause harmful interference and This device must accept any interference received, including interference that may cause undesired operation.
  • Page 4: Man_905G_1.16

    Notice in operating procedures and system manuals. These products should not be used in non-industrial applications, or life-support systems, without consulting ELPRO Technologies first. For 905G modules, a radio license is not required in most countries, provided the module is installed using the aerial and equipment configuration described in the 905U Installation Guide.
  • Page 5: How To Use This Manual

    Chapter Four Configuration explains how to configure the modules using the Configuration Software available. Chapter Six Troubleshooting will help if your system has problems. The foldout sheet 905U-G Installation Guide is an installation drawing appropriate for most applications. Page 5...
  • Page 6: Table Of Contents

    Contents CONTENTS CHAPTER 1 INTRODUCTION 1.1 905G O VERVIEW 1.1.1 Modbus / DF1 905G 1.1.2 Profibus 905G 1.1.3 Ethernet 905G 1.1.4 DeviceNet 905G 1.1.5 Modbus Plus 905G 1.2 T 905G S TRUCTURE 1.2.1 On-board I/O 1.2.2 I/O Expansion - 105S modules 1.3 T IRELESS ETWORK...
  • Page 7 905U-G Wireless Gateway User Manual 4.2.2 Security 4.3 M 905G 905U I/O M APPINGS ODULES 4.3.1 Mappings from Inputs at Remote 905U I/O Modules 4.3.2 Mappings from 905G to Outputs at Remote 905U I/O Modules 4.3.3 Don’t Send if in Comm Fail 4.3.4...
  • Page 8 Contents 6.4 F IELDBUS NDICATING CHAPTER 7 WARRANTY APPENDIX 1 STATUS REGISTERS APPENDIX 2 IT FUNCTIONALITY MAN_905G_1.16 Page 8...
  • Page 9: Chapter 1 Introduction

    905U-G Wireless Gateway User Manual Chapter 1 INTRODUCTION 1.1 905G Overview The 905U-G Wireless Gateway products provide a wireless interface between various fieldbus protocols used in process and automation applications. The 905U-G includes an integral 905U I/O 900MHz license-free radio transceiver, and...
  • Page 10: Modbus / Df1 905G

    Chapter One Introduction The 905U-G is referred to as the 905G for the rest of this document, to clearly differentiate from normal 905U I/O modules. Ordering information: 905U-G-MD1 Modbus Master & Slave / DF1 interface 905U-G-PR1 Profibus-DP Slave interface 905U-G-PR2...
  • Page 11: Ethernet 905G

    905U-G Wireless Gateway User Manual The Profibus 905G I/O database has 4300 registers (each of 16 bit value), however the Profibus interface limits the amount of I/O that can be transferred via the Profibus port. Slave unit (PR1). The PR1 slave unit only supports 416 x 8 bit bytes of I/O. Of the 416 bytes of I/O, there is a maximum 244 input bytes and maximum 244 output bytes - that is, if 244 input bytes are used then only 172 output bytes can be used (416 –...
  • Page 12: Devicenet 905G

    Chapter One Introduction byte can be 8 discrete inputs or outputs, but analog or pulse I/O take up 1 byte for low resolution values (8-bit) or 2 bytes for high resolution values (16-bit). An “output” is a value coming into the 905G via the fieldbus. An input is a value going out from the 905G via the fieldbus.
  • Page 13: The 905G Structure

    905U-G Wireless Gateway User Manual 1.2 The 905G Structure The 905G has three functional sections: • The Radio Interface consists of an I/O database (or "Process Image") that maintains the latest values of all I/O in the wireless I/O system. The I/O database comprises 4300 x 16 bit I/O registers and 4300 x 16 bit status registers.
  • Page 14: On-Board I/O

    RS485 port of the 905G modules. Note: 105S modules cannot be connected to the 905U-G-MD1 unit (as this unit uses the RS485 port for Modbus or DF1 communications), unless this unit is configured as “Repeater-only”...
  • Page 15: To 905G Network

    905U-G Wireless Gateway User Manual 905U modules can transmit input messages directly to outputs on other 905U-3 905U module, as well as the 905G. The same input can be transmitted to different addresses by entering two "mapping" 905U-K configurations at the remote module.
  • Page 16: Data Concentrator" Networks

    Chapter One Introduction As well as the normal “I/O change” messages and update messages, the 905G has “block read” and “block write” messages for use with other 905G modules. These messages will transmit multiple register values instead of only one as in the normal 905U message. The block read/write messages increase the efficiency of radio communications where a 905G “sees”...
  • Page 17: Repeaters

    Where a 905G is being used without a host device as a repeater or data-concentrator, it can be configured as “Repeater-only”. This allows the RS232/485 port to be used for on-line diagnostics. If the unit is a 905U-G-MD1, the “Repeater-only” configuration also allows this module to connect to 105S serial I/O modules.
  • Page 18: Chapter 2 Operation

    905U-G Wireless Gateway User Manual Chapter 2 OPERATION 2.1 Start-up The 905G operating software and the database configuration are stored in non-volatile memory, however the database I/O register values are lost on power failure (in the same way as a PLC).
  • Page 19 DIN1 905U-1 905U-G An example of normal operation - assume that a remote module has address 14 and the 905G is address 1. Module #14 is configured with a mapping DI1 → I/O Reg 76 at #1.
  • Page 20: Database

    905U-G Wireless Gateway User Manual 2.3 Database The 905G database (Radio Interface) has 10 000 registers, each of 16 bit size. The structure of the database is: Registers Purpose 0 - 4299 I/O registers 4300 - 4399 On-board I/O 4401 - 4499 Comms-fail status and radio strengths for remote modules...
  • Page 21: The Host - 905G Link

    “HOST DEVICE” 2.4.1 Modbus / DF1 The user selects whether the 905U-G-MD1 should act as a Modbus Master or Modbus Slave or DF1 device. The data type and baud rate of the serial communications must be configured at the 905G to match the host.
  • Page 22: Profibus

    905U-G Wireless Gateway User Manual 2.4.2 Profibus The Profibus port has auto-detect of baud rate from 9600 bits/sec to 12Mbit/sec - no configuration is required. The Profibus units have internal hardware comprising the Profibus Interface. The Profibus Interface handles all Profibus DP Network communications. The internal Radio Interface is separate to the Profibus Interface, and handles all radio communications.
  • Page 23: Radio Signal Strength

    Chapter Two Operation Each 905U module can have up to 31 x 105S modules connected to it. These modules are addressed 96 - 127. More than one 105S module can have the same address, provided they are not connected to the same 905U module - that is, #100 via #16 is identified as a different module to #100 via #65.
  • Page 24: Monitoring Communications Failure

    905U-G Wireless Gateway User Manual For I/O registers which are mapped to a remote output or another 905G, the comms fail status is set if the 905G does not receive an acknowledgment for a message being sent to that remote output. The comms fail status resets when a successful transmission occurs.
  • Page 25: Security Considerations

    Chapter Two Operation comms problem (this means that the corresponding update time for the input at the 905U will need to be short). If the point is an output, then the update time for the output should be made short. 2.7 Security Considerations There are three dimensions of security considerations: 1.
  • Page 26: Chapter 3 Installation

    Alternately, use an intermediate 905U Module as a repeater. The foldout sheet 905U-G Installation Guide provides an installation drawing appropriate to most applications. Further information is detailed below.
  • Page 27 Chapter Three Installation antennas inside buildings. An obstructed path requires testing to determine if the path will be reliable - refer the section 6 of this manual. Where it is not possible to achieve reliable communications between two modules, then another 905U or 905G module may be used to receive the message and re-transmit it.
  • Page 28: Dipole And Collinear Antennas

    905U-G Wireless Gateway User Manual Where antennas are mounted on elevated masts, the masts should be effectively earthed to avoid lightning surges. For high lightning risk areas, surge suppression devices between the module and the antenna are recommended. If the antenna is not already shielded from lightning strike by an adjacent earthed structure, a lightning rod should be installed above the antenna to provide shielding.
  • Page 29: Power Supply

    Chapter Three Installation The Yagi gain also acts on the receiver, so adding Yagi antennas at both ends of a link provides a double improvement. Yagi antennas are directional. That is, they have positive gain Antenna installed to the front of the antenna, but with drain holes negative gain in other down...
  • Page 30: Ac Supply

    905U-G Wireless Gateway User Manual 3.3.1 AC Supply The AC supply is connected to the “SUP1” and “SUP2” terminals as shown below. The AC supply should be “floating” relative to earth. Power SUP1 12 – 24 VAC Supply SUP2 AC Out...
  • Page 31: Solar Supply

    Chapter Three Installation On return of normal supply, the unit will recharge the battery. The maximum output of the battery charger is 0.7A when the supply voltage is greater than 12V, and 0.3A for less than 12V. The 105G monitors the power supply and provides the following internal values, which can be mapped as I/O values: •...
  • Page 32: Serial Port

    905U-G Wireless Gateway User Manual All eight of the 105G DIO terminals may also be used as discrete outputs. The digital outputs are transistor switched DC signals, FET output to common rated at 30VDC 500 mA. Digital outputs may be configured to individually turn off if no command message is received to that output for a certain period.
  • Page 33: Rs485 Serial Port

    Hardware handshaking using the CTS/RTS lines is provided, and are under the control of the Host Comms Driver. Example cable drawings for connection to a DTE host (a PC) or another DCE host are detailed below: 905U-G 905U-G 3.5.2 RS485 Serial Port RS485 should not be used with the DF1 unit.
  • Page 34 905U-G Wireless Gateway User Manual It is important to maintain the polarity of the two RS485 wires. On the 905G, terminal A (the terminal on the right) is positive and terminal B is negative. Page 35 ©September 2004...
  • Page 35: Profibus Port

    Chapter Three Installation 3.6 Profibus Port The Profibus RS485 connector is a D9 connector in the top end-plate of the module (see below). 905U-G-PR1 (Profibus Slave) End Plate: RS485 PROFIBUS D9 SELECTOR DIAGNOSTIC TERMINATION CONNECTOR SWITCHES LED’s SWITCH CONFIGURATION ENABLE...
  • Page 36: Ethernet Port

    RS485 (Negative) Not connected 3.7 Ethernet Port For 905U-G-ET1 modules only. The Ethernet connection uses a standard RJ45 connector on the top end-plate of the module. The selector switches should all be “off” (in the diagram below, “off” is up).
  • Page 37: Modbus Plus Port

    Chapter Three Installation 3.8 Modbus Plus Port For 905U-G-M+1 modules only. Connection to the Modbus Plus Network is via the 9-pin D-SUB connector located at the antenna end of the module. Pin-outs are outlined in the table below. D9 MODBUS...
  • Page 38: Devicenet Port

    905U-G Wireless Gateway User Manual 3.9 DeviceNet Port For 905U-G-DE1 modules only. Connection to the DeviceNet Network is via the 5-pin plugable screw terminal connector located at the antenna end of the module. Pin-outs are specified below. DEVICENET SELECTOR DIAGNOSTIC...
  • Page 39: Chapter 4 Configuration

    905U-G Wireless Gateway User Manual Chapter 4 CONFIGURATION 4.1 Introduction A Windows program is provided to configure the 905U system. The configuration is done on a system basis - referred to as a “project” in the program. After the system configuration is entered, the configuration file can be loaded into each module via the RS232 port.
  • Page 40: Configuration Program

    Chapter 4 Configuration 4.2 Configuration Program The configuration software is available on a CD, and needs to be installed on your PC before you can use it. The CD contains a setup file called setup.exe. Select the configuration software window on the Product CD and an installation Wizard will guide you through the installation procedure.
  • Page 41 905U-G Wireless Gateway User Manual screen will appear where you may enter the system address. If you are editing an existing project, the system address will already have been entered. Do not change the system address unless you are going to re- program all of the modules in the system.
  • Page 42 Select the type of module from the list. For 905G modules, you will be asked to select the bus protocol. This must match the 905U-G module type you have installed. You have the option of selecting a unit address for the module, or allowing the program to select one automatically.
  • Page 43 905U-G Wireless Gateway User Manual Deleting a Unit A module can be deleted from the configuration by highlighting the unit and selecting “Delete Unit”. Page 45 ©September 2004...
  • Page 44: Security

    Chapter 4 Configuration 4.2.2 Security There are two security features available. You can enter a password to protect the configuration files, and you can enable security encryption of the radio transmissions. The password can be between 6 and 256 characters. The password is case sensitive and any ASCII characters can be used.
  • Page 45 Note on Ethernet 905U-G. You are able to access the module configuration of an Ethernet 905G via the Ethernet port. To prevent this access, do not select “Enable Ethernet Debug” on the Ethernet configuration display - see section 4.8.
  • Page 46: Mappings 905G To 905U I/O Modules

    Chapter 4 Configuration 4.3 Mappings 905G to 905U I/O Modules To transfer remote input signals to a 905G, or transfer a value to a remote output from a 905G, you set up “I/O mappings”. You enter mappings into the source unit, not the destination unit.
  • Page 47 905U-G Wireless Gateway User Manual Any I/O registers that have already been selected will have a color shading. The update times, analog sensitivities for these mappings can be set as per normal I/O mappings. To map several inputs to consecutive I/O registers, use “Shift”-select or “Ctrl” - select to highlight the inputs, and select the first I/O register in the range.
  • Page 48: Mappings From 905G To Outputs At Remote 905U I/O Modules

    Chapter 4 Configuration To set the comms fail times, select the 905G, and select the “Comms Fail Time” option. Each remote input already mapped to the 905G will automatically be listed, including the remote module containing the mapping. The default value for the comms-fail time is “disabled” or zero. To enter a time, select the I/O register from the list.
  • Page 49 905U-G Wireless Gateway User Manual You can configure the amount of change required to trigger a change message - this is called the change sensitivity. Sensitivities are configured for blocks of I/O registers - that is, each I/O register does not have a unique sensitivity. You can configure up to 50 sensitivity values - that is, there can be 50 blocks of registers with different sensitivities.
  • Page 50: Don't Send If In Comm Fail

    Chapter 4 Configuration Update Times To change the update times of output mappings, select the Update Times option. Any I/O registers that have already been mapped to remote outputs will automatically be listed. The default update time is 10 minutes. Changing Multiple Settings You can change the Comms Fail Times or Update Times of several I/O points simultaneously by using the <Shift>...
  • Page 51: Startup Polls

    905U-G Wireless Gateway User Manual To configure this special mapping, select the “New Don’t Send in Comms Fail Mapping” box. You will be asked to select which remote module this function applies to. You can enter more than one of these mappings if there are more than one modules.
  • Page 52 Chapter 4 Configuration Read/Write Mappings The mappings can be “read” or “write” mappings. A Read mapping is a request sent to another 905G to return a block of values. A Write mapping is a message sending a block of values to another 905G. A Read mapping from 905G#2 to 905G#3 could be the same as a Write mapping from 905G#3 to 905G#2 (that is, in the reverse direction) - except the Read mapping is initiated from #2 and the Write mapping is initiated from #3.
  • Page 53: Entering A Block Mapping

    905U-G Wireless Gateway User Manual 4.4.1 Entering a Block Mapping Select the “source” 905G on the left hand menu - select “Block Mappings” and then “New Block Mapping” from the right-hand display. The Block Mapping Configuration display will appear. Select the “Command Type” from the pop-down window in the centre of the display. The red arrow will confirm the direction of the block transfer.
  • Page 54: Host Device Trigger

    Chapter 4 Configuration In the above example, the status register for the block mapping has been automatically assigned to register 9500. The rest of the mapping configuration involves the mapping trigger - or what initiates the mapping message. Mapping “Triggers” A block mapping can be “triggered”...
  • Page 55: Time Period

    905U-G Wireless Gateway User Manual 4.4.3 Time Period On the Block Mapping display, there are two configuration windows - “Period” and “Offset” - these determine the time period trigger and real-time trigger. For a time-period trigger, select “Continuous” in the “Period” pop-down window. Under “Offset”...
  • Page 56: Real-Time

    Chapter 4 Configuration 4.4.4 Real-Time The block mapping message can be sent at a real-time by setting the “Period” value. In this example, “period” is set to 6 minutes - the message will be sent every 6 minutes starting at the beginning of each hour.
  • Page 57 905U-G Wireless Gateway User Manual 4333. On power-up, these registers are set to zero. Reg 4333 increments each second, Reg 4332 increments each minute, Reg 4331 each hour and Reg 4330 each day. The clock registers are used by the 905G for the real-time-clock trigger. The host device can read these registers.
  • Page 58: Change-Of-State

    Chapter 4 Configuration 4.4.5 Change-of-State If a value in the block changes by more than the sensitivity amount, then the block message will be sent (this can only occur for Write mappings). The sensitivity values are set under the “Sensitivity” option as per section 4.5. A delay time can be entered to reduce the number of change triggers in active systems.
  • Page 59: Repeater-Only" Configuration

    905U-G Wireless Gateway User Manual 4.4.8 “Repeater-only” Configuration Any 905G module can act as a repeater unit. However a 905G may need to be installed as a repeater only (that is, there is no host device connected). In this case, the base 905G, the 905U- G-MD1 unit would normally be used as this is the lowest cost of the 105G modules.
  • Page 60 Chapter 4 Configuration trigger will occur for register 34. Sensitivity values are in decimal and can vary between 1 and 65535 (16-bit). Up to 50 blocks of sensitivities can be configured. If a register is included in more than one block, then the first sensitivity value configured will be accepted and later values ignored.
  • Page 61: Serial Configuration - Modbus

    User Manual 4.6 Serial Configuration - MODBUS The 905U-G-MD1 module provides interface for Modbus Slave, Modbus Master and Allen- Bradley DF1. This Modbus interface uses the Modbus RTU protocol - also known as the Modbus Binary protocol. This manual assumes that the reader has a good understanding of the Modbus or DF1 protocol.
  • Page 62 Chapter 4 Configuration Supported Modbus Function Codes: Function Meaning Code Read the state of multiple digital output points Read the state of multiple digital input points Read the value of multiple output registers Read the value of multiple input registers Set a single digital output ON or OFF Set the value of a single output register Read Exception Status - compatibility - returns zero...
  • Page 63: Modbus Master

    905U-G Wireless Gateway User Manual Supported Exception Codes: Exceptio Name Description n Code Illegal function The module does not support the function code in the query Illegal data address The data address received in the query is outside the initialized memory area...
  • Page 64 Chapter 4 Configuration command is a “Digital” write, meaning that the register values will be written as digital/binary values”. If the Modbus Slave device does not respond to the Modbus command, the 905G will try another 3 times (“Max Retries” = 3). The Modbus command will be sent to the Modbus Slave every 100msec.
  • Page 65 905U-G Wireless Gateway User Manual To complete the Fieldbus Configuration, enter any other Modbus commands that may be required to transfer I/O points between the 905G and the Modbus Slave devices. Digital I/O The value of a digital I/O point is stored in the 905G database as a hexadecimal '0000' (“off”) or hex 'FFFF' (“on”).
  • Page 66: Serial Configuration - Df1

    Chapter 4 Configuration When updated values are received from the 905U radio network, the current polling sequence is interrupted, and the new values are written immediately to the appropriate slaves. Re-tries on the Serial Port When communicating with Modbus slaves, the 905G may be configured to re-try (or re-send) a message zero or more times if no response is received from a slave.
  • Page 67 905U-G Wireless Gateway User Manual Command Description Code Function Comment Code Protected Write 0x00 PLC2 series and SLC / Micrologix NONE Unprotected Read 0x01 PLC2 series and SLC / Micrologix NONE Diagnostic Status 0x06 Diagnostic Commands 0x00 Echo message 0x06...
  • Page 68 Chapter 4 Configuration If the 905G acts as a command initiator, you can enter a “Request Delay” between commands sent to the host. To enter a DF1 command, select “New Serial Mapping”. The following example is a file write command which writes 905G I/O registers 80 – 104 (25 registers) to DF1 files I3.1 to I27.1 at DF1 address 2.
  • Page 69 905U-G Wireless Gateway User Manual Discrete I/O The value of a digital I/O point is stored in the 905G database as a hexadecimal '0000' (“off”) or hex 'FFFF' (“on”). However the 905G will generate either a ‘0’ (“off”) or ‘1’ (“on”) to a binary file when initiating a “Typed Logical Write”...
  • Page 70 Chapter 4 Configuration then mask out the high 16 bits (MVM with mask value FFFF). This will result in a long integer value in the range 0 to 65535. Alternatively, use a long integer file type to transfer the analog value as a long integer in the range 0-65535.
  • Page 71: Fieldbus Configuration

    905U-G Wireless Gateway User Manual 4.8 Fieldbus Configuration All 905G modules (except MD1) have separate internal hardware comprising the Fieldbus Interface, consisting of a separate microprocessor and appropriate hardware for the network connection. This Fieldbus Interface handles all fieldbus communications, and transfers I/O in the Fieldbus Interface Registers to/from the fieldbus.
  • Page 72: Fieldbus Mappings

    Chapter 4 Configuration Radio Interface Fieldbus Interface IN Area Profibus 244 Bytes Modbus/TCP 2048 Bytes Ethernet/IP allows 6 input connections; each Write Read from from connection Max 512 bytes Host Modbus Plus 2048 bytes DeviceNet 512 bytes 10,000 x 16-bit I/O Registers OUT Area Profibus 244 Bytes...
  • Page 73 905U-G Wireless Gateway User Manual Fieldbus Mapping Types Transfer Mode Read Mapping Write Mapping The 905G reads a block of The 905G takes the MSB (most Single Bit consecutive bits from Fieldbus OUT significant bit) of a block of Area and stores each bit in...
  • Page 74 Chapter 4 Configuration The Fieldbus Interface IN and OUT areas are simply a block of I/O memory, exchanged according to the configured protocol. For example, with a Profibus slave that supports 244 bytes of inputs, the fieldbus interface IN area could be addressed either as byte locations 1 to 244 or as word locations 1 to 122.
  • Page 75 905U-G Wireless Gateway User Manual Three Fieldbus Mappings are illustrated in the example above. Note that “Word Address Mode” is selected, meaning that the Fieldbus Interface IN and OUT Areas will be treated as word-addressed arrays by configuration software. The parameters for each fieldbus mapping were setup using the mapping configuration screen as described above.
  • Page 76 Chapter 4 Configuration The first Fieldbus Mapping is a “Write WORD” mapping, writing I/O Registers 10 – 15 from the Radio Interface to word-locations 1 – 5 in the Fieldbus IN Area. Because the transfer mode is “word” complete 16-bit registers are transferred. The second mapping is a “Read BIT”...
  • Page 77: Fieldbus Configuration - Profibus Slave

    The Profibus 905U-G-PR1 acts as a Profibus DP Slave - the host device is a Profibus Master. If you use the 905U-G with a PLC, the PLC configuration tool will require a GSD file so it can recognize the Profibus interface in the 905U-G. This file loads into the PLC configuration software (for example, Siemens STEP 7).
  • Page 78: Fieldbus Configuration - Profibus Master

    Configuration 4.10 Fieldbus Configuration - Profibus Master The 905U-G-PR2 implements a complete Profibus-DPV0/DPV1 master. The hardware is optimized for high throughput and can be used in mono or multi master networks up to 12 Mbit/s. Up to 125 slaves with a total max of 2048 byte input and 2048 byte output data can be connected.
  • Page 79 905U-G Wireless Gateway User Manual 4.10.3 Configuration Profibus network configuration is performed via the ESeries Configuration Utility. The 905G Profibus Master provides up to 2048 bytes of inputs and 2048 bytes of outputs in the fieldbus interface for I/O on the profibus network. I/O in the fieldbus interface must be linked with I/O in the radio interface via appropriate fieldbus mappings (see 4.8 Fieldbus...
  • Page 80: Configuration

    Chapter 4 Configuration selected in the busview so that the network list is displayed in the listview rather than the slave I/O configuration list). The above example shows a slave device being added to the network at node address 7. Slave Address To change the node address of a slave already configured on the network, locate the slave in the network listview and drag it to the position in the list corresponding to the desired...
  • Page 81 905U-G Wireless Gateway User Manual Group Assignment If the slave supports sync/freeze functionality, it can be assigned to the masters sync/freeze groups by clicking on the checkboxes. The sync/freeze assignment of the groups is also displayed (these can be changed via the master properties dialog).
  • Page 82 Chapter 4 Configuration be edited directly (consult the device specific documentation for the meaning of these values). Adding I/O to a Slave The possible I/O combinations for a given slave may be fixed or configurable (i.e. modular) depending on the GSD file for the device. When the I/O configuration is fixed, the fixed I/O are always defined whenever the device is added to the network.
  • Page 83 905U-G Wireless Gateway User Manual I/O modules may also have associated user parameter data defined by the corresponding GSD file. The meaning of these parameters (if applicable) is specific to the slave implementation, and may be altered via the Parameter Assignment tab of the Module Properties form.
  • Page 84 Chapter 4 Configuration parameters (see Bus Parameters Tab below). The storage format determines if word values are stored in big endian (Motorola – most significant byte has lowest address) or little endian (Intel – Least significant byte has lowest address) format. Group Properties Tab A DP master can send the SYNC and/or FREEZE control commands simultaneously to a group of slaves for synchronization purposes.
  • Page 85 905U-G Wireless Gateway User Manual Tqui The quiet time is the time a modulator needs after recognizing a send frame to switch from send to receive. 0 t_bit <= Tqui <= MIN(31 t_bit, Min. Tsdr - 1) Gap Factor The Gap Factor determines how many token rounds occur before a new active node (master) can be added to the token ring.
  • Page 86 Chapter 4 Configuration 256 t_bit <= Ttr <= 16.776.960 t_bit Non-adjustable bus parameters The target rotation time determines the maximum available time for a token pass. During this time all active nodes (masters) obtain the token one time to send data. ESeries Config Software calculates an optimized Ttr depending on the values of other bus parameters.
  • Page 87 905U-G Wireless Gateway User Manual Configuration Example: The Following example describes a simple configuration of a 905G connected to a simple Profibus Slave I/O device. Described is the configuration of the local 905G Profibus master only, for more detailed configuration examples, an application note can be downloaded from www.elprotech.com.
  • Page 88 Chapter 4 Configuration 2) Fieldbus Configuration. The next configuration step is to transfer the I/O in the Fieldbus Interace to the Radio Interface so that the profibus I/O is available to the radio network. The 8 x digital output to be sent to the profibus slave are transferred using a fieldbus write mapping.
  • Page 89 905U-G Wireless Gateway User Manual 3) Radio Configuration To complete the configuration, the I/O that has now been transferred to the radio interface must be mapped over the radio network. The analog input from the slave is mapped to an...
  • Page 90: Message Interface

    Chapter 4 Configuration 4.10.4 Message Interface In addition to cyclic data exchange with slave devices, the 905G Profibus Master also supports a number of acyclcic services that may be triggered via a special Message Interface. The message interface is by default disabled, but will become enabled by also enabling a “Status Location”...
  • Page 91 905U-G Wireless Gateway User Manual The message interface supports the following types of communication: • Command - Response A message is sent by the message initiator, and the message recipient is required to respond. The message initiator can be either the 905G or host device.
  • Page 92 Chapter 4 Configuration Message Information This register contains information about whether the message is a command or a response, and may also indicate an error (see below). b15 b14 b13 b12 b11 b10 (reserved) Error Code Message Type For example, a command message will always contain the value 4002h in this register. A response message will contain 0002h, and may contain error information as detailed in the table below.
  • Page 93 905U-G Wireless Gateway User Manual Extended Words 1 ... 8 These registers are specific for each command. Consult the specification for each command for further information. Message Interface Addressing Command messages and response messages are allocated fixed locations in the radio interface (I/O Registers).
  • Page 94 Chapter 4 Configuration Set Slave Mode SET_SLAVE_MODE: Command Number = 0003h. In addition to station related user data transfer, which is executed automatically, the master can send control commands to a single slave, a group of slaves or all slaves simultaneously. These control commands are transmitted as multicast commands.
  • Page 95 905U-G Wireless Gateway User Manual This parameter decides which group should be addressed, see below. bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 Group 8 Group 7 Group 6 Group 5 Group 4...
  • Page 96 Chapter 4 Configuration Get Slave Diagnostics GET_SLAVE_DIAG: Command Number = 0004h This command reads diagnostic data from a specified slave. Note: The response data size depends on the actual slave implementation. Range 6 -244. Command and response layout: Command Response Message ID (ID) (ID)
  • Page 97 905U-G Wireless Gateway User Manual Address of the master that parameterized the slave • Ident Number Unique ID assigned by the Profibus User Organization • Extended Diagnostic Data Slave user specific diagnostic data. Consult the documentation for the actual slave for further information.
  • Page 98 Chapter 4 Configuration Set Slave Address SET_SLAVE_ADDRESS: Command Number = 0006h This command makes it possible to set the node address of a specified slave, provided that the slave supports this feature. Note: The message data size depends on the actual slave implementation; range 0 -240 bytes. Command and response layout: Command Response...
  • Page 99 905U-G Wireless Gateway User Manual 00h: Change of address is still possible at a later stage 01h-FFh: Change of address only possible after the initial address (i.e. default address = 126) • Error Code [1 ...4 ] If ‘Return Code ’ equals 8030h (‘Negative indication from lower layer ’), status values according to the DP-specification are available in ‘Error Code 1 ’.
  • Page 100 Chapter 4 Configuration Get Live List GET_LIVE_LIST: Command Number = 0018h This command returns 127 bytes of information about the nodes on the network. Every byte stands for one bus subscriber, and the position of the byte in the response data assigns the address Command and response layout: Command...
  • Page 101 905U-G Wireless Gateway User Manual DPV1 Acyclic Read MSAC1_READ: Command Number = 0020h This command initiates a DPV1 Class 1 acyclic read request. Consult EN50170 (DPV1) for more information. Command and response layout: Command Response (ID) (ID) Message ID Message Information...
  • Page 102 Chapter 4 Configuration See "Return Codes" in section “DP Error Codes ” below. • Fault Information If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here. 0001h: Address out of range 000Ah:...
  • Page 103 905U-G Wireless Gateway User Manual DPV1 Acyclic Write MSAC1_WRITE: Command Number = 0021h This command initiates a DPV1 Class 1 acyclic write request. Consult EN50170 (DPV1) for more information. Command and response layout: Command Response (ID) (ID) Message ID Message Information...
  • Page 104 Chapter 4 Configuration If ‘Invalid Other ’is returned in the Message Information word in the header of the response, information about the fault can be found here. 0001h: Address out of range 000Ah: Failed to execute MSAC1_Alarm_Ack request 000Bh: Remote station failure 0010h: Remote Station DPV1 Failure (see ‘Error Decode’...
  • Page 105 905U-G Wireless Gateway User Manual Alarm Indication MSAL1_ALARM_IND: Command Number = 0022h This message indicates that a DPV1 slave has transferred an Alarm message to the master. This message is sent spontaneously by the 905G, i.e. the module itself initiates the message instruction in the “Spontaneous Message OUT Area”...
  • Page 106 Chapter 4 Configuration Range 0 -31 • Alarm Spec Ack Gives additional information about the Alarm, such as an error appears, or disappears. It also indicates whether the slave needs additional acknowledge from the Master (Example: Writing to a certain memory area with an Acyclic Write request). Range 0 -7 •...
  • Page 107 905U-G Wireless Gateway User Manual Alarm Confirmation FB_ABM_MSAL1_ALARM_CON: Command Number = 0023h This message indicates that a slave has confirmed a previous MSAC1_Alarm_Ack, see “Alarm Indication (MSAL1_ALARM_IND)” above. This message is sent spontaneously by the 905G, i.e. the module itself initiates the message instruction in the “Spontaneous Message OUT Area”...
  • Page 108 Chapter 4 Configuration Range 0 -7 • Alarm Type Identifies the alarm type, such as Process Alarm, Plug Alarm etc. Range 1 -6, 32 -126 • Extended Diagnostic Flag FFh: Slave sends an alarm message with “Extended Diag flag ”set 00h: Slave sends an alarm message with “Extended Diag flag ”cleared •...
  • Page 109 905U-G Wireless Gateway User Manual 4.10.5 DP Return Codes Possible DP error codes in Message Data word ‘Return Code ’ Return Name Meaning Code 8010h DPMC_ERR_V1C_CLOSED Internal DPMC instance no longer exists. 8011h DPMC_ERR_V1C_STOPPED Internal DPMC instance already stopped 8012h...
  • Page 110: Error Codes

    Chapter 4 Configuration Error Codes If return code indicates ‘DPMC_ERR_V1C_REQ_NEG ’, the status values according to the DP-standard may be available in ‘Error Code 1 ’ (See below). Consult the Profibus DP specification for information on how to interpret these status values. Error Code Name Meaning...
  • Page 111: Dpv1 Return Codes

    905U-G Wireless Gateway User Manual DPV1 Return Codes Possible DPV1 related Error Codes in Message Data word ‘Return Code’ Return Name Meaning Code 0003h DPMC_ERR_M_MEM_ALLOC Internal memory allocation error 0004h DPMC_ERR_M_L2_REQ Unknown opcode in the confirmation 0005h DPMC_ERR_M_INVALID_PAR Invalid parameter in user request...
  • Page 112: Setting Ip Address

    Chapter 4 Configuration 1. Modbus/TCP. The module supports the Modbus/TCP protocol and conforms to the Modbus/TCP specification 1.0 (full information on this protocol can be obtained from http://www.modicon.com/openmbus/index.html). Refer to section 4.10.2 below for configuration details. 2. EtherNet/IP. EtherNet/IP is based on the Allen-Bradley Control and Information protocol, CIP, which is also the framework for both DeviceNet and ControlNet, to carry and exchange data between nodes.
  • Page 113 905U-G Wireless Gateway User Manual An IP Address is divided into two main parts subnet ID and host ID. All devices on the same local network must have the same subnet ID, but a unique host ID. To separate these two parts a subnet mask is used.
  • Page 114: Modbus Tcp

    Chapter 4 Configuration Enable Ethernet Debug Select this box if you wish to enable Ethernet Diagnostics on the 905G via configuration software (see section 6.3 for details). For security reasons, disabling this option will disallow all Ethernet diagnostics functions accessible to configuration software, and can only be reactivated via serial port configuration.
  • Page 115 905U-G Wireless Gateway User Manual also enabled, the “Disable I/O Instance” option must be selected for each fieldbus mapping to which Modbus/TCP Addressing is to apply. IN Area Modbus TCP Addresses (905G Write Locations 0 – 1023*) Modbus Modbus Bit Address...
  • Page 116 Chapter 4 Configuration The Fieldbus IN and OUT areas can be configured to a maximum size of 1024 words (2048 bytes) each, depending on the configured fieldbus mappings. The highest mapped location will correspond to the highest available Modbus register (or coil) available to a Modbus/TCP client.
  • Page 117: Ethernet/Ip

    The rest of this section assumes the reader is familiar with Ethernet/IP. If you use the 905U-G with a PLC, the PLC confiuration tool will require an EDS file so it can recognize the Ethernet/IP interface in the 905U-G. The file is available on the same CD as the configuration software, or on the ELPRO web site.
  • Page 118 Chapter 4 Configuration To make I/O data available via Ethernet/IP, ensure that the Enable Ethernet/IP checkbox on the Ethernet Settings page is checked. Appropriate Fieldbus Mappings need to be configured to link the required I/O registers to the Fieldbus Interface, as described above in the Profibus and Modbus/TCP sections.
  • Page 119 905U-G Wireless Gateway User Manual Assembly Object, Class 04h The Assembly Object binds all mapped I/O data. This data is used for I/O connections. This object is set-up dynamically via fieldbus mappings through configuration software. Class Attributes: Def, Name Service...
  • Page 120 Chapter 4 Configuration I/O Data Input Mapping Object, Class A0h This object is setup dynamically via fieldbus read mappings through configuration software. This data is also available as vendor specific Instance Attributes (64h to 69h) in the Assembly Object. Class Attributes: Def, Name Service...
  • Page 121: Fieldbus Configuration - Devicenet

    905U-G Wireless Gateway User Manual 4.12 Fieldbus Configuration – DeviceNet 4.12.1 DeviceNet Introduction DeviceNet is a broadcast-oriented communications protocol based on the Controller Area Network (CAN). The physical fieldbus is a shielded copper cable composed of one twisted pair and two cables for the external power supply. The baud rate can be changed between 125k, 250k, and 500kbit/s via Configuration Software or DIP-switch.
  • Page 122: Protocol And Supported Functions

    Chapter 4 Configuration network configuration. The EDS file can either be downloaded from the ELPRO website (www.elprotech.com), or found on the Product CD supplied with the module. 4.12.4 Protocol and Supported Functions The 905G DeviceNet module is implemented according to the ODVA specification for a communication adapter (profile no 12) and acts as a group two only server on the DeviceNet network.
  • Page 123: Protocol & Supported Functions

    905U-G Wireless Gateway User Manual configuration is the recommended option if use of the GDB Offset and Count parameters is required (see section 4.11.4). Two sets of six switches are available: Node Address (S1, the left-most set of switches, closest to the D-SUB connector), and Source Address (S2, the right-most set of switches).
  • Page 124: Configuration

    Chapter 4 Configuration range is 40001 – 41024 of which the first 32 words (i.e. 40001 – 40032) are global output data. However all output registers, including the global output registers, may also be read from the module using the point-to-point command Read Holding Registers (0x03). The possible input registers (Data From Network) range is 41025 –...
  • Page 125 905U-G Wireless Gateway User Manual Finally, it must be taken into consideration that the 905G Modbus Plus module dynamically adjusts the 4X register range available to the network depending on the fieldbus mappings configured. The 905G will terminate the available 4X register range at the last mapped 4X register for both the read and write area.
  • Page 126: Connecting 105S Serial I/O

    NOTE – Serial I/O Expansion is only possible for 105G Firmware versions 1.50 onwards. 105S modules can be connected to the RS485 port of all 905G units except for the 905U-G- MD1 unit. 105S modules can be connected to the MD1 if the 905G is configured as “Repeater-only”...
  • Page 127: Uploading And Downloading

    905U-G Wireless Gateway User Manual 4.15 Uploading and Downloading To upload or download a configuration file, the 905G must be connected to the PC via a RS232 cable. For Modbus/DF1 units, the host device must be disconnected, even if it is connected to the RS485 port.
  • Page 128 Chapter 4 Configuration If you are unable to load into the archived project, then mappings to remote modules will be displayed, but mappings from remote inputs will be shown as “Unknown Mappings”. If you also load the configurations from the other remote modules in the system, then these unknown mappings will disappear as the program can determine where the remote inputs are.
  • Page 129: Chapter 5 Specifications

    905U-G Wireless Gateway User Manual Chapter 5 SPECIFICATIONS General EMC approval FCC Part 15A Radio standards FCC Part 15.247 902 – 928 MHz, 1W Housing 130 x 185 x 60mm Powder-coated, extruded aluminum DIN rail mount Terminal blocks Removable Suitable for 12 gauge / 2.5 mm...
  • Page 130 Chapter 5 Specifcations Frequency USA/Canada 902 – 928 MHz Australia 915 – 928 MHz New Zealand 922 – 928 MHz Transmission Power Signal detect / RSSI -120 to –40 dBm Expected line-of-sight range 20 miles + @ 4W ERP USA / Canada (subject to local conditions) 15 km + @ 1W ERP Australia / New Zealand...
  • Page 131: Chapter 6 Diagnostics

    905U-G Wireless Gateway User Manual Chapter 6 DIAGNOSTICS Before installing a new system, it is always best to set up the system on a bench to test the system configuration. It is always easier to detect problems when the modules are together.
  • Page 132: Diagnostics Menu

    Chapter 6 Diagnostics 6.2 Diagnostics Menu The 905G provides both offline and online diagnostic features to assist with troubleshooting. The offline diagnostics disable both the radio and fieldbus interface drivers, and are only used for simple radio tests such as “RSSI Measurement” or “Tone Reversals”. The online diagnostics provide more powerful debugging features such as access to the internal I/O Registers and Radio Communications Monitoring while the module is running (i.e.
  • Page 133 905U-G Wireless Gateway User Manual 6.2.1 Offline Diagnostics: The offline diagnostics menu disables the radio protocol driver and the fieldbus protocol driver. Before displaying the offline debug menu open and start the “terminal” window in configuration software (see above), or use any third party terminal package.
  • Page 134 Chapter 6 Diagnostics 130 dBm). If the average noise is greater than –105, the difference between the noise level and the transmitter signal should be at least 10dB for reliable operation. For example, if the average noise level is -101dBm, then a transmitter signal of better than -91dBm is required for reliable operation.
  • Page 135 905U-G Wireless Gateway User Manual The online diagnostics menu is also referred to as the “Debug” menu. The Debug Menu allows the Radio Interface (I/O Registers) to be viewed and modified to confirm the operation of the radio network. These options may be used to check operation of outputs at remote sites, and to check the values of inputs reported from remote sites.
  • Page 136 Chapter 6 Diagnostics Press “Enter” to go back to the menu. Option b) Write Image Array This option allows you to change the value of an I/O register in the Radio Interface. To change the value of a register, select option b) write image array. Enter the location, then the value to be written to the register –...
  • Page 137 905U-G Wireless Gateway User Manual now expects the 905G to be in monitor comms mode, and will decode all radio communications. The display will show radio messages transmitted and received. Messages starting with RX are received messages, CMD are transmitted messages and ACK are acknowledgment messages.
  • Page 138 Chapter 6 Diagnostics then the value in the Fieldbus database will overwrite the I/O register and you may get an incorrect value. When doing read/write image array and the module has been configured with Fieldbus mappings, you may need to disable the Fieldbus read area option h. This stops the Fieldbus database overwriting the radio database.
  • Page 139: Ethernet Diagnostics

    905U-G Wireless Gateway User Manual 6.3 Ethernet Diagnostics Read and Write image array can also be done via the Ethernet port by selecting ‘Debug I/O Registers’ from within the Ethernet Settings window in the configuration software. The IP address of the...
  • Page 140 Chapter 6 Diagnostics To write to a register double click with mouse on the register and a pop up box will appear as shown below. Enter value and press ‘OK’. You can disable the links between the I/O registers and the Ethernet interface by selecting “Disable Read Area”...
  • Page 141: Fieldbus Indicating Leds

    905U-G Wireless Gateway User Manual 6.4 Fieldbus Indicating LEDs All 905G modules (except MD1) are equipped with four fieldbus indication LED's located in the module end plate, used for diagnostics purposes. The meaning of the LED’s for each fieldbus is described below.
  • Page 142 Chapter 6 Diagnostics 6.4.2 Profibus Slave Indicating LED’s LED No Indication Description Not Used Green Module is On-Line and data exchange is possible. Module is not On-Line Module is Off-Line and no data exchange is possible. Module is not Off-Line Flashing Red 1 Error in configuration: IN and/or OUT length set during initialization of the module is not equal to the length set during...
  • Page 143 905U-G Wireless Gateway User Manual 6.4.3 Profibus Master Indicating LED’s LED No Indication Description 1. Master Status Green Operate mode Green, flashing Clear mode Stop mode Offline 2. Database Status Green Database OK Green, flashing Database download in progress Database invalid No database downloaded 4.
  • Page 144 Chapter 6 Diagnostics 6.4.4 Modbus Plus Indicating LED’s LED No Indication Description Not Used Active Red ERROR; This led indicates that communication is not OK. Green MBP Active; This led flashes in different patterns depending on the module’s health (see below). Flash every 160 ms;...
  • Page 145 905U-G Wireless Gateway User Manual 6.4.5 DeviceNet Indicating LED’s: Led No Color State Description Reserved for future use Not powered / Not online Green Steady Link OK, On line, Connected Green Flashing On line, Not connected Flashing Connection timeout Steady...
  • Page 146: Chapter 7 Warranty

    905U-G Wireless Gateway User Manual Chapter 7 WARRANTY We are pleased that you have purchased this product. ELPRO products are warranted to be free from manufacturing defects for a period of 2 years from the effective date of purchase. The effective date of purchase is decided solely by ELPRO Technologies.
  • Page 147: Appendix 1 Status Registers

    905U-G Wireless Gateway User Manual Appendix 1 Status Registers I/O Status Registers 5000 - 9499 Information Meaning Communications For inputs, this bit is set (“on”) if no message has been received from failure the remote address within the timeout period configured for this input.
  • Page 148 Appendix 1 Block Message Status Registers 9500 - 9999 Information Meaning Communication For read commands – Read Bits and Read Words – This bit is set if no s failure response is received to the read command after a timeout, or if a communication fail response is received to a read.
  • Page 149: Appendix 2 It Functionality

    User Manual Appendix 2 IT Functionality 905U-G-ET1 Ethernet module only Filesystem The filesystem is a fixed-size storage area with a hierarchical directory structure. Any user- or application data can be stored in files within the filesystem. Files can be grouped in directories for increased readability.
  • Page 150 Appendix 2 IT Functionlity • Admin Mode Admin users have full access to the filesystem through FTP and Telnet. This enables the user to access areas of the filesystem that are restricted or inaccessible in Normal mode. The Admin user accounts are defined in the file ‘ad_pswd.cfg’. If no admin password file (See “System Files”) is found or Admin Mode is set by configuration software, the module will run in Admin Mode;...
  • Page 151 905U-G Wireless Gateway User Manual may be present in the system, allowing different users to access different files and directories. The file format is the same as for the ‘ad_pswd.cfg’ and ‘sys_pswd.cfg’ files, except that the optional parameter ‘AuthName’ can be added. The value of this parameter will be presented in the login window.
  • Page 152 Appendix 2 IT Functionlity The contents of this file can be redirected by placing the line ‘[File path]’ on the first row, and a file path on the second. This procedure is exactly the same as with the system file “web_accs.cfg” (see above). telwel.cfg The default Telnet welcome message can be changed by creating this file.
  • Page 153 905U-G Wireless Gateway User Manual The figure below illustrates the structure of the file system, where the system files are located, and which areas Normal/Admin users can access. The files and directory structure must be created by the user using FTP or Telnet. The required .cfg file structures are outlined in the ‘System Files’...
  • Page 154 Appendix 2 IT Functionlity \config.htm - Configuration frame page \configform.htm - Configuration form page \configform2.htm - Configuration form page \store.htm - Configuration store page \logo.jpg - HMS logo \configuration.gif - Configuration picture \boarder.bg.gif - picture \boarder_m_bg.gif - picture FTP Server It is possible to upload/download files to/from the file system using a standard FTP client.
  • Page 155 905U-G Wireless Gateway User Manual Syntax: <?--#exec cmd_argument=’DisplayDNS2’--> This function returns the address of the secondary DNS server DisplayHostName Syntax: <?--#exec cmd_argument=’DisplayHostName’--> This function returns the hostname. DisplayDomainName Syntax: <?--#exec cmd_argument=’DisplayDomainName’--> This function returns the default domain name. DisplayDchpState Syntax: <?--#exec cmd_argument=’DisplayDhcpState( "Output when ON", "Output when...
  • Page 156 Appendix 2 IT Functionlity This SSI function includes a formatted string, which may contain data from the Fieldbus IN/OUT area, on a web page. The formatting of the string is equal to the standard C function printf(). Like the standard C function printf() the "String to write" for this SSI function contains two types of objects: Ordinary characters, which are copied to the output stream, and conversion specifications, each of which causes conversion and printing of the next successive argument to printf.
  • Page 157 905U-G Wireless Gateway User Manual The conversion characters and their meanings are shown below. If the character after the % is not a conversion character, the behaviour is undefined. Char- Argument Converted to acter type d, i byte, word decimal notation (For signed representation. Use signed argument) byte, word octal notation (without a leading zero).
  • Page 158 Appendix 2 IT Functionlity The arguments that can be passed to the SSI function printf are: Argument Description InReadSByte( offse t) Reads a signed byte from position offset in the IN area InReadUByte( offse t) Reads an unsigned byte from position offset in the IN area InReadSWord( offse t) Reads a signed word (short) from position offset in the IN area InReadUWord( offse t)
  • Page 159 905U-G Wireless Gateway User Manual Character Input data, Argument Type Decimal number; byte, short Number, byte, short. The number may be in octal (leading 0(zero)) or hexadecimal (leading 0x or 0X) Octal number (with or without leading zero); byte, short Unsigned decimal number;...
  • Page 160 Appendix 2 IT Functionlity This SSI function saves the contents of a passed form to a file. The passed name/value pair will be written to the file "File name" separated by the "Separator" string. The contents can either be Appended to the file or overwrite the current content of the file. Default output: Success - Form saved to file...
  • Page 161 905U-G Wireless Gateway User Manual Parameter Description Area Source Fieldbus Interface Area. Possible values are ‘IN’ or ‘OUT’ Offset Source offset in Fieldbus Area, shall be written in decimal or hexadecimal. Type Source data type. Possible values are ‘byte’, ‘word’, and ‘long’...
  • Page 162 Appendix 2 IT Functionlity Note: If the [Register] or [Register match] information is changed, a reset is required for changes to take effect. Other changes will take effect directly without a reset. Note: Hexadecimal values must be written in the format 0xN where ‘N’ is the hexadecimal value.
  • Page 163 905U-G Wireless Gateway User Manual This command will display version information, serial number and MAC ID exit This command closes the Telnet session. Diagnostic Commands The following commands can be viewed by the command ‘help diagnostic’ arps Display ARP stats and table...
  • Page 164 Appendix 2 IT Functionlity Syntax: del [[path][filename]] Deletes a file. Syntax: ren [[path][old name]] [[path][new name]] Renames a file or directory. move Syntax: move [[source path][source file]] [[destination path]] This command moves a file or directory from the source location to a specified destination.

Table of Contents