It could take maximum 60 minutes to operate for the protection of the compressor. if the outdoor
temperature is below -5°C.
Ampere Limit Setting & Changing Procedure
WARNING
◆ Do not adjust the "Ampere Limit Switch", if it' s not necessary :
before modifying it, evaluate the total number of electric and electronics
loads consumption and use "Ampere limits switch" just as
emergency solution or in case the system is anyway oversized compared to
real thermal load needed.
◆ "Ampere Limit Switch" is initially set to the default value (table below).
◆ "Ampere Limit Switch" is on the PCB of outdoor unit.
◆ Contact the authorized service technician or dealer for setting and changing
the "Ampere Limit Switch".
◆ Before changing the "Ampere Limit Switch", turn off the main power of the
system.
RJ040F2HX ** RJ050F2HX ** RJ060F3HX ** RJ070F4HX **
9.0A
11.0A
(Default)
(Default)
8.5A
9.0A
8.0A
8.0A
7.0A
7.0A
Ampere
Switch
RJ080F4HX **
13.0A
16.6A
(Default)
(Default)
(OFF)
13.0A
14.0A
(OFF)
10.0A
11.0A
(OFF)
8.0A
10.0A
(OFF)
※ The designs and shape are subject to
change according to the model.
RJ040F2HX ** /RJ050F2HX **
Switch
Selection
3
4
ON
ON
RJ060F3HX ** /RJ070F4HX **
ON
OFF
OFF
ON
OFF
OFF
Outdoor PCB Display
SW0 2
RJ080F4HX **
31