Protection Control For Heating Operation - Panasonic CS-E24LKES Service Manual

Indoor/outdoor unit
Hide thumbs Also See for CS-E24LKES:
Table of Contents

Advertisement

2. Control contents
• Operation stops.
• Timer LED blinks and "H99" indicated.
13.2.7. Odor Cut Control
• To reduce the odor released from the unit.
- Start Condition
- AUTO FAN Speed is selected during COOL or DRY operation.
- During freeze prevention control and timer preliminary operation, this control is not applicable.
- Control content
- Depends on compressor conditions:
1. Compressor OFF → Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor ON → Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.

13.3. Protection Control For Heating Operation

13.3.1. Intake Air Temperature Control
Compressor will operate at limited frequency if indoor intake air temperature is 30°C or above.
13.3.2. Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor
overloading.
13.3.3. Overload Protection Control
The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below figures.
13.3.4. Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
13.3.5. Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor and outdoor fan
motor stop and operation LED blinks.
50

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-e24lkeCs-e28lkesCu-e28lke

Table of Contents