<Packed valve handling precautions>
• Open the valve stem all the way out, but do not try
to open it beyond the stopper.
Pipe size of Packed Valve
12.70 mm and smallers
15.88 mm
• Securely tighten the valve cap with torque in the
following table
Cap
Cap Size (H)
H17 - H19
Valve Rod
Cap
H22 - H30
H14
Service
Port Cap
H17
Hexagon wrench
is required.
CAUTION
Service Port Cap
Valve Rod Cap

10-4-5. Electrical Work

1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with
the air conditioner.
NOTE
Wire type : More than H07RN-F or 60245 IEC66
(1.5 mm
CAUTION
Connection to fixed wiring :
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporated in the fixed
wiring. An approved circuit breaker or switches
switched must be used.
• Perform wiring works so as to allow a general
wiring capacity.
Size of Hexagon wrench
A = 4 mm
A = 5 mm
Torque
14~18 N.m
(1.4 to 1.8 kgf·m)
33~42 N.m
(3.3 to 4.2 kgf·m)
8~12 N.m
(0.8 to 1.2 kgf·m)
14~18 N.m
(1.4 to 1.8 kgf·m)
A
H
Fig. 10-4-9
2
or more)
10-4-6. Wiring Connection
1. Remove the valve cover from the outdoor unit.
2. Connect power cord to the terminal block
and
then connect the connecting
cable to the terminals as identifed with their
respective matched numbers on the terminal
block of indoor and outdoor unit.
3. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed
them so that they do not touch any electrical or
or metal parts.
<Stripping length of connecting cable>
RAS-13, 16N3KV2 Series
Terminal
block
Connecting
cable
RAS-10N3KV2 Series
Terminal
block
Connecting
cable
Model
RAS-10N3KV2-A
Power source
Maximum
running current
Circuit breaker
Power cord
Connecting
cable
– 66 –
FILE NO. SVM-13001
Revi110
Earth line
Power
cord
Connecting cable
Earth line
Power
cord
Connecting cable
Fig. 10-4-10
RAS-13N3KV2-A
50Hz, 220 - 240 V Single phase
8.5A
9.1A
11.0A
12.0A
H07RN-F or 60245 IEC66
2
(1.5 mm or more)
H07RN-F or 60245 IEC66
2
(1.0 mm or more)
L, N
Earth line
Power cord
Earth line
Power cord
RAS-16N3KV2-A
11.0A
14.0A