7-2. Operation Data
<Cooling>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
27/19
35/-
10N3KV2-A
13N3KV2-A
16N3KV2-A
<Heating>
Tempeature
Model name
condition(°C)
RAS-
Indoor
Outdoor
20/-
7/6
10N3KV2-A
13N3KV2-A
16N3KV2-A
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Heat exchanger
Standard
pipe temp.
pressure
P (MPa)
T1 (°C)
0.9 to 1.1
12 to 14
0.8 to 1.0
11 to 13
0.8 to 1.0
11 to 13
Standard
Heat exchanger
pipe temp.
pressure
P (MPa)
T1 (°C)
2.5 to 2.7
39 to 41
2.6 to 2.8
41 to 43
2.7 to 2.9
43 to 45
– 25 –
Indoor
fan mode
T2 (°C)
37 to 39
High
46 to 48
High
40 to 42
High
Indoor
fan mode
T2 (°C)
0 to 3
High
0 to 2
High
0 to 2
High
FILE NO. SVM-13001
Outdoor
Compressor
fan mode
revolution
(rps)
High
49
High
59
High
67
Outdoor
Compressor
fan mode
revolution
(rps)
High
60
High
66
High
67