<When the installation plate is directly
mounted on the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook
up the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts. use the anchor bolt holes as
illustrated in the below figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with mount-
ing screw, do not use the anchor bolt holes.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
(Keep horizontal direction.)
5 mm dia. hole
Clip anchor
(local parts)
Fig. 10-3-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the
unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting
7
screws
.
NOTE :
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Anchor bolt
Projection
15 mm or less
7 Mounting screw
∅4 x 25 s
– 58 –
10-3-3. Wiring Connection
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot
on the rear panel so that it protrudes from the front
show on the figure below.
5. Insert the connecting cable fully into the
block and secure it tightly with screws.
6. Tighten firmly but not over 1.2 N.m (0.12 kgf.m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Terminal block
Cord
clamp
Terminal cover
Screw
Screw
100 mm
10 mm
3
10 mm
90 mm
Stripping length of the connecting cable
NOTE :
• Use stranded wire only.
• Wire type : More than H07RN-F or 60245 IEC66
2
(1.0 mm
or more.)
FILE NO. SVM-13001
terminal
Connecting cable
Earth line