Honeywell T7200D Product Data page 30

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Model
Number
T8621B7018
BDP multi-logo; LOW and HIGH SPEED LEDs;
used on multispeed equipment;
part no. HH07AX012.
T8621B7026
Honeywell logo; TRADELINE® model; Premier
White® color; direct replacement for T8621B7000
and T8621B7018.
T8621C
Two-stage heat and one-stage cool conventional thermostat; two transformer capability;
system switch: HEAT-AUTO-COOL-OFF; fan switch: ON-AUTO.
T8621C7008
Honeywell logo; TRADELINE® model.
T8621C7016
Honeywell logo; Canadian TRADELINE® model.
T8621C7032
Trane logo; system switch: HEAT-OFF-COOL;
one transformer; dual fuel switch;
part no. TAYSTAT302.
T8621D
Two-stage heat and two-stage cool conventional thermostat; two transformer capability;
system switch: HEAT-AUTO-COOL-OFF; fan: ON-AUTO.
T8621D7006
Honeywell logo; TRADELINE® model.
T8621D7014
Honeywell logo; Canadian TRADELINE® model.
T8621D7022
Honeywell logo; TRADELINE® model; system
switch: HEAT-OFF-COOL; dual fuel switch; O
and B terminals.
T8621D7030
Trane logo; part no. THT-0607; order
no. 13510323-17-7.
T8621D7048
BDP multi-logo.
T8621D7055
Lennox logo; one transformer capability;
part no. 27H2901.
T8621D7063
Trol-A-Temp® by Honeywell logo; system switch:
HEAT-OFF-COOL; O and B terminals.
T8621D7071
Trol-A-Temp® by Honeywell logo; no system or
fan switching.
T8621D7089
Carrier logo; part no. HH641-103.
T8621D7097
Honeywell logo; TRADELINE® model; remote
sensor capability.
T8621D7105
Friedrich logo; L terminal; extra switch for louver
control; part no. 616-789-01.
T8621D7113
Honeywell Logo; Canadian TRADELINE®
Premier White® color model.
63-4355—1
Table 16. Thermostat and Subbase Cross Reference (Continued) .
Description
Trade Replacement
T7300D2007/Q7300A2008
T7300D2007/Q7300A2008
T7300D2007/Q7300A2040
T7300D2007/Q7300A2040
T7300D2007/Q7300A2040
T7300D2007/Q7300A2008
T7300D2007/Q7300A2008
T7300D2007/Q7300A2057
T7300D2007/ Q7300A2008
T7300D2007/Q7300A2008
T7300D2007/Q7300A2008
None
None
T7300D2007/Q7300A2008
T7300D2007/Q7300A2008
None
T7300D2007/Q7300A2008
30
Remarks
Wiring differences
(old=new): L=X1; X4 to X
and RC to RH field-installed
jumper required.
Wiring differences
(old=new): L=X1; X4 to X
and RC to RH field-installed
jumper required.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): B=X; RC to RH
field-installed jumper
required.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X. RC to RH
field-installed jumper
required.
Wiring differences
(old=new): C=X; see Trol-A-
Temp® repre-sentative for
replacement.
See Trol-A-Temp® repre-
sentative for replacement.
Wiring differences
(old=new): C=X.
Wiring differences
(old=new): C=X; purchase
new remote
2-wire sensors separately.
See OEM for replacement
information.
Wiring differences
(old=new): C=X.
(Continued)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents