T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Electrical Rating:
24 Vac, 50/60 Hz.
20 to 30 Vac, 50/60 Hz.
Batteries:
No batteries required.
Auxiliary Heat and Emergency Heat Indication:
Thermostat display indicates when Auxiliary Heat or
Emergency Heat are activated.
Loss of Power:
The thermostat will maintain programmed times and
temperatures for the life of the product. The clock and day
information is retained for a minimum of two hours.
Light Emitting Diodes (LEDs):
Two user-defined LEDs.
Two defined (CHECK and MAINTENANCE) LEDs on
select models.
Two additional LEDs available on select models.
System Current Draw:
6 VA maximum at 30 Vac, 50/60 Hz.
Output Relay Draw:
See Table 3.
Table 3. Maximum Amps at 30 Vac.
Relay
Fan
Heat (all stages)
Cool (all stages)
Auxiliary (Economizer)
Temperature:
Ratings:
Operating Ambient: 40°F to 110°F (4°C to 43°C).
Shipping: -30°F to +150°F (-34°C to +65°C).
Display Accuracy:
±1°F (±0.5°C).
Setpoint:
Range: 45°F to 95°F (7°C to 35°C).
Differential: 2°F (1°C).
Default Settings: see Table 4.
Table 4. Default Setpoints.
Control
Occupied
Heating
70°F (20°C)
Cooling
78°F (25.5°C)
Remote Sensor Wiring Temperature Offset:
Temperature offset occurs with 500 ft (157m) to 1000 ft (305m)
of 2-wire cable. See Table 5.
Running (A)
Inrush (A)
1.6
3.5
1.6
3.5
1.6
7.5
1.6
3.5
Unoccupied
55°F (13°C)
90°F (32°C)
Table 5. Temperature Offset.
Temperature
Range
18 AWG
50-90°F
10-32°C
Minimum Stage Operation Time:
Minimum On (Heat and Cool): factory setting 2 minutes;
option 0 minutes.
Minimum Off (Cool and Heat Pump): factory setting
4 minutes; option 0, 1, 3, 5 minutes.
Humidity Ratings:
5% to 90% RH, noncondensing.
Clock Accuracy:
+1 minute per month.
Finish:
Taupe color.
Dimensions:
See Fig. 1.
Mounting Means:
T7200 Thermostat mounts on a wallplate. The T7300 Thermo-
stat mounts on a Q7300 Subbase. The wallplate and
subbase mount horizontally on a wall or outlet box with two
no. 6 x 32 screws (included).
Accessories:
C7150B Discharge Air Sensor (form 63-2072).
C7400 Enthalpy Sensor (form 63-2140).
M7415 Damper Actuator (form 63-2100).
ML7984 Valve Actuator (form 95C-10753).
R8222 Switching Relay (form 60-2056).
T675A Temperature Control (form 60-2200).
T7022A1010 Remote Temperature Sensor (form 60-0247).
T7047C Remote Temperature Sensor (form 62-3050).
T7047G Remote Temperature Sensor (form 62-3050).
T7147A Remote Temperature Sensor and Override
Module (form 62-3049).
W859F Packaged Economizer (form 63-2476).
W950A System Supervisor (form 60-2351).
W7459 Economizer Logic Module (form 63-2141).
W6210/W7210 Economizer (form 63-2528).
Approvals:
CE listed
RECYCLING NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of the old thermostat.
3
20 AWG
22 AWG
-0.4°F
-0.7°F
-1.0°F
-0.3°C
-0.4°C
-0.6°C
63-4355—1