Honeywell T7200D Product Data page 12

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Installer Setup
Number
(Press
Unoccupied
Temp key
to change)
Select
Intelligent Fan™
17
operation
Not used
18
Extended fan
19
operation in
a
heating
Extended fan
20
operation in
cooling
Fan key adjust-
21
ment (models
with Fan key)
Remote sensing
22
Temperature
23
averaging
b
network
Not used
24
Keypad lockout
25
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)
Duration of
26
temporary
override
Not used
27 thru 29
Deadband
30
Interstage
31
control point
(Q7300C,D only)
b
Number 22 must be set to 1 and remote sensor(s) must be installed.
63-4355—1
Table 8. Thermostat Installer Setup Options (Continued).
Factory-Setting
Display
Description
2
Fan operates con-
tinuously in Occupied
and recovery modes.
Fan operates with call
for heating or cooling in
Unoccupied mode.
0
No extended fan
operation after the call
for heat ends
0
No extended fan
operation after the call
for cool ends
0
Fan setting key is
operational
0
Remote sensing not
activated
0
Temperature averaging
disabled
0
No lockout
3
3—Three hour override 1, 8 or 12 1—One hour override
2
Heating and cooling
setpoints can be set no
closer than 2°F
0
Disabled
Other Choices
(Press
or
Display
0 or 1
0—Fan only operates with calls for
heating or cooling in Occupied
and Unoccupied modes
1—Fan operates continuously in
Occupied mode. Fan operates
with calls for heating or cooling in
Unoccupied mode.
1
Fan operation is extended
90 seconds after the call for
heat ends.
1
Fan operation is extended
90 seconds after the call for
cool ends.
1
Fan setting key is Auto only
1
Remote sensing activated
1
Temperature averaging between
local sensor and remote sensor(s)
activated
1 or 2
1—Lockout all keys on thermostat
except system and fan settings,
temporary setpoint, clock and
day adjustments
2—Lockout all keys except Set
Current Day/Time, increase
and decrease
8—Eight hour override
12—Twelve hour override
3 thru 10 Heating and cooling setpoints can
be set no closer than the chosen
value
1 thru 12 Temperature has to change more
than the chosen value before the
system calls for the next stage.
(Example: 68°F is the heat setpoint,
2°F is the interstage setting,
temperature is 65.5°F, the second
stage turns on, brings the
temperature to 66°F and turns off.
The heat pump continues to run until
the setpoint is met.)
12
key to change)
Actual
Setting
Description
keys
(Continued)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents