LG LS-J0910CL Service Manual page 24

Room air conditioner
Hide thumbs Also See for LS-J0910CL:
Table of Contents

Advertisement

(1) Installation Parts Provided
1. Type "A" screw
2. Installation Plate
3. Type "B" screw
4. Holder Remote Control
(2) Installation of indoor, outdoor unit
Read completely, then follow step by step.
1) Select the best location
1. Indoor unit
Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the
unit.
Make sure that condensation drainage can be convenient-
ly routed away.
Do not install near a doorway.
Ensure that the space around the left and right of the unit
is more than 5cm(2"). The unit should be installed as high
on the wall as possible, allowing a minimum of 5cm(2")
from ceiling.
Use a stud finder to locate studs to prevent unnecessary
damage to the wall.
More than
5cm(2")
More than 2.3m(7.5ft)
Install the indoor unit on the wall where the height from the
floors more than 2.3 meters(7.5ft).
2. Outdoor unit
If an awning is built over the unit to prevent direct sunlight
or rain exposure, make sure that heat radiation from the
condenser is not restricted.
Ensure that the space around the back and sides is more
than 10cm. The front of the unit should have more than
70cm of space.
Do not place animals and plants in the path of the warm
air.
Take the air conditioner weight into account and select a
place where noise and vibration are minimum.
Select a place so that the warm air and noise from the air
conditioner do not disturb neighbors.
More than 5cm(2")
More than
5cm(2")
CAUTION
More than
10cm(4")
More than
70cm(28")
Rooftop Installations:
If the outdoor unit is installed on a roof structure, be sure to
level the unit. Ensure the roof structure and anchoring
method are adequate for the unit location. Consult local
codes regarding rooftop mounting.
2) Piping length and elevation
Pipe Size
MODEL
(Cooling Capa.)
GAS LIQUID
9K, 12K
1/2"
18K
5/8"
24K
5/8"
Indoor unit
In case more than 5m(16.4ft)
• Capacity is based on standard length and maximum
allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7 meters(16.4~23ft).
- 24 -
More than 60cm(24")
More than 10cm(4")
More
than 60cm(24")
Max
length
A
1/4"
15m(50ft)
1/4"
15m(50ft)
3/8"
15m(50ft)
Outdoor unit
A
B
Outdoor unit
A
Oil trap
Indoor unit
B
CAUTION
Max
Elevation
B
8m(26ft)
8m(26ft)
8m(26ft)