4. Auto Operation (Electronic control mode)
• The operation procedure is shown below. (Cooling & Heating Model)
Operation mode
Indoor fan speed
Setting temperature
Intake-air
temperature
Operation Mode
If initial mode is decided, that mode is continued without the room temperature changing.
Auto Operation for Cooling
Operation Condition
When Auto Operation
initial start
When pressing room
temperature setting
button during Auto
Operation
INTAKE AIR TEMP.
SETTING TEMP. +1°F
(Compressor OFF)
SETTING TEMP. -1°F
(Compressor ON)
INDOOR FAN SPEED
COMPRESSOR
Press Start/Stop Button
Select Auto Operation Mode
Check the Room temperature
are decided automatically by the unit electronic control.
below 70°F
Heating
Intake-air Temperature
Over 78°F
Over 76°F~below 78°F
Over 72°F~below 76°F
Over 68°F~below 72°F
Intake air temperature
below 64°F
Over 64°F~below 86°F
below 64°F
over 86°F
The electronic control operation
ON
- 16 -
Over
below
~
70°F
Soft Dry
Setting Temperature
77°F
Intake air -1°C
Intake air -0.5°C
Controlled by
the electronic
control
64°F
Electronic control
64°F
86°F
OFF
Over 76°F
76°F
Cooling
Fan Speed
Air Direction Control
In this mode,
when pressing
the vertical air
direction control
button, vertical
louver swings up
and down
automatically.
ON
OFF