6. Heating Operation Mode(only Heating Model)
The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. + 6°F
(Compressor OFF)
SETTING TEMP.
(Compressor ON)
INDOOR FAN SPEED
COMPRESSOR
• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the
indoor pipe temperature becomes lower than 95°F, indoor fan stops.
• B point; When the indoor pipe temperature is higher than 38°C(100°F), fan operates at selected fan speed.
Hot-Start Control
• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.
• During heating operation, if indoor pipe temperature falls below 78°F fan stops.
• The operation diagram is shown below.
INDOOR PIPE
INDOOR FAN SPEED
COMPRESSOR
minimum
Selecting
fan speed
ON
TEMP.
82°F
78°F
OFF
A
B
minimum
1 min.
10sec.
Low
OFF
Low
OFF
1min
Selecting
LOW
fan speed
ON
- 19 -