Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Heat exchanger
Fan(drive) o No.
Fan motor output
Airflow
Crankcase heater
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Notes1. Rating Conditions (JIS B8616)
Cooling : Indoor
: 27˚C(80˚F)DB. 19˚C (66˚F)WB
Heating : Indoor
: 20˚C(68˚F)DB.
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Cooling
Lower limit
Upper limit
Heating
Lower limit
3. Above deta based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
kW
A
A
kW
Internal thermostat, Anti-phase protector, thermal relay, HP switch, Discharge thermo, LP switch
kW
K/min(CFM)
W
dB(A)
Cooling
dB(A)
Heating
mm,(in.)
W
mm,(in.)
D
mm,(in.)
H
kg,(lbs)
kg,(lbs)
cc
mm,(in.)
Liquid
mm,(in.)
Gas
Indoor side
Outdoor side
Height difference
Piping length
Outdoor : 35˚C(95˚F)DB. 24˚C (75˚F)WB
Outdoor : 7˚C(45˚F)DB. 6˚C (43˚F)WB
Outdoor
Indoor
32˚C DB, 23˚C WB
43˚C DB
21˚C DB, 15˚C WB
-5˚C DB
27˚C DB
24˚C DB, 18˚C WB
20˚C DB
-5˚C DB, -6˚C WB
PUH-P5YGA
Cooling
Heating
3-ph, 50Hz, 380-415V(4wires)
5.25
5.47
8.39
8.74
79
Munsell 5Y 8/1
Linear Expansion Valve
HE86YAA
4.3
Plate fin coil
Propeller (direct) o 2
0.075+0.075
95(3,360)
Reverse cycle
53
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
2,000(Ester)MEL32
7
PUH-P6YGA
Cooling
6.36
10.17
84
Hermetic
HE101YAA
5.1
Line start
100(3,530)
38
55
57
122(269)
R407C
5.8(12.8)
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Heating
6.43
10.28