Mitsubishi Electric PUHY-RP200 Service Handbook page 44

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Same as [5] 1.
ŒOnly use shielded cables.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on the
outdoor units (OC) in different refrigerant circuits and on
the OC, OS1, and OS2 in the same refrigerant circuit
If a power supply unit is not connected to the transmis-
sion line for centralized control, replace the power jump-
er connector on the control board from CN41 to CN40 on
only one of the outdoor units.
The outdoor units in the same refrigerant circuit are au-
tomatically designated as OC, OS1, and OS2 in the or-
der of capacity from large to small (if two or more units
have the same capacity, in the order of address from
small to large).
(5) Address setting method
Proce-
Unit or controller
dures
1
Indoor
Main unit
unit
Sub unit
2
LOSSNAY
3
MA
Main
re-
remote
mote
controller
con-
Sub
troller
remote
controller
4
Outdoor unit
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have
the same capacity, in the order of address from small to large).
HWE10010
Address setting
range
IC
01 to 50
LC
01 to 50
MA
No
settings required.
MA
Sub
remote controller
OC
51 to 100
OS1
OS2
- 35 -
35
ŒOnly use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on
the outdoor units (OC, OS1, OS2) with the shield wire of
the shielded cable. Short-circuit the earth terminal (
and the S terminal on the terminal block (TB7) on the out-
door unit whose power jumper connector is mated with
CN40.
3) MA remote controller wiring
Same as [5] 1.
When 2 remote controllers are connected to the sys-
tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 2.
4) LOSSNAY connection
Same as [5] 2.
5) Switch setting
Address setting is required as follows.
Setting method
Assign the smallest ad-
dress to the main unit in
the group.
Assign sequential num-
bers starting with the ad-
dress of the main unit in
the same group +1. (Main
unit address +1, main unit
address +2, main unit ad-
dress +3, etc.)
Assign an arbitrary but
unique address to each of
these units after assigning
an address to all indoor
units.
-
Settings to be made ac-
cording to the remote con-
troller function selection
Assign sequential address
to the outdoor units in the
same refrigerant circuit.
The outdoor units are au-
tomatically designated as
OC, OS1, and OS2.
(Note)
Factory
Notes
setting
To perform a group
operation of indoor
units that have differ-
ent functions, desig-
nate the indoor unit in
the group with the
greatest number of
functions as the main
unit.
None of these ad-
dresses may overlap
any of the indoor unit
addresses.
Main
To set the address to
100, set the rotary
switches to 50.
)
00
00
00
GB

Advertisement

Table of Contents
loading

Table of Contents