Mitsubishi Electric PUHY-RP200 Service Handbook page 135

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10010
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-RP300YJM-A
20°C/- [68°F/- ]
7°C/6°C
[45°F/43°F]
4
4
-
125/80/63/32
10 [32-3/4]
5 [16-3/8]
30 [98]
-
Hi
kg
14.3 [32]
A
17.4
V
400
Hz
84
315/246/432/184
-
-
2.88/0.71
[418/103]
76 [169]
12 [54]
1 [34]
3 [37]
3 [37]
22 [72]
35 [95]
63 [145]
- 126 -
Outdoor unit model
PUHY-RP350YJM-A
20°C/- [68°F/- ]
7°C/6°C
[45°F/43°F]
4
4
140/125/63/32
10 [32-3/4]
5 [16-3/8]
30 [98]
Hi
15.6 [35]
21.3
400
101
365/386/432/241
-
-
2.96/0.68
[429/99]
79 [174]
11 [52]
0 [32]
2 [36]
2 [36]
21 [70]
36 [97]
64 [147]
GB