Mitsubishi Electric PUHY-RP200 Service Handbook page 33

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
System configu-
Connection to
ration
the system con-
troller
System with
one outdoor unit
System with
Not connected
multiple outdoor
units
With connection
to the indoor
unit system
With connection
to the central-
ized control
system
*1 The need for a power supply unit for transmission lines depends on the system configuration.
*2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
Connection to the system controller
Connection to the system controller
*1 Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting.
*2 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor
on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON.
ŒSome models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
ŒWhen using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON.
ŒWhen using an optional temperature sensor, install it where room temperature can be detected.
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by
*1,*2,*3
the plug
Automatic restoration
after power failure
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
crankcase heater and may cause the compressor to malfunction when the unit is put back into operation.
*2. Not applicable to units with a built-in drain pump or humidifier.
*3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug.
*4. Requires that the dipswitch settings for all the units in the group be made.
*5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
HWE10010
Power supply unit
for transmission
lines
_
_
_
Not required
*1
Not required
(Powered from the
outdoor unit)
1
Required *
System configuration
Not connected
Connected *
Operation of the indoor unit when the operation is resumed after the unit was
Indoor unit will go into operation regardless of its operation status before power
off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was
turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before power
off (power failure).
Group operation
Power supply switch connector connection
of units in a sys-
tem with multiple
outdoor units
_
Leave CN41 as it is
(Factory setting)
Not grouped
Grouped
Disconnect the male connector from the fe-
male power supply switch connector (CN41)
Grouped/not
and connect it to the female power supply
grouped
switch connector (CN40) on only one of the
outdoor units.
*Connect the S (shielded) terminal on the ter-
Grouped/not
grouped
Grouped/not
Leave CN41 as it is
grouped
(Factory setting)
Centralized control switch settings *
Leave it to OFF. (Factory setting)
2
ON
stopped
- 24 -
*2
minal block (TB7) on the outdoor unit whose
CN41 was replaced with CN40 to the
ground terminal ( ) on the electric box.
Setting (SW1)
1
*4 *5
9
10
OFF
ON
ON
OFF
OFF
OFF
GB

Advertisement

Table of Contents
loading

Table of Contents