Mitsubishi Electric PUHY-RP200 Service Handbook page 142

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
(2) Heating operation
Ambient
tempera-
ture
Indoor
unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC (LEV1)
ing
LEV2
High pressure (after O/S)/low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10010
Operation
Indoor
DB/WB
Outdoor
No. of connected
units
Unit
No. of units in opera-
tion
Model
Main pipe
Branch pipe
m [ ft ]
Total pipe length
[ lbs-oz ]
Pulse
MPa
[ psi ]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
°C [ °F ]
Compressor inlet
Compressor shell
bottom
LEV inlet
Heat exchanger
outlet
PUHY-RP200YJM-A
-
-
kg
A
V
Hz
54
-
-
2.60/0.72
[377/104]
73 [163]
12 [54]
1 [34]
3 [37]
3 [37]
22 [72]
33 [91]
61 [142]
- 133 -
Outdoor unit model
PUHY-RP400YSJM-A
PUHY-RP200YJM-A
20°C/- [68°F/- ]
7°C/6°C
[45°F/43°F]
4
4
200/100/63/32
10 [32-3/4]
5 [16-3/8]
30 [98]
Hi
20.6 [46]
18.4
400
54
315/315/432/241
2.60/0.72
[377/104]
73 [163]
12 [54]
1 [34]
3 [37]
3 [37]
22 [72]
33 [91]
61 [142]
-
-
GB