[ VII Microprocessor Control ]
Remote controller setting is not acceptable.
3. Drain pump
(1) Same control as COOL operation

3. Fan operation

TIME SUN MON TUE WED THU FRI SAT
TIMER
AFTER
˚F˚C
ONLY1Hr.
TEMP.
MENU
BACK
MONITOR/SET
PAR-21MAA
CLOCK
1. Fan
(1) Set by remote controller.
3 speeds + Auto type
When [Auto] is set, fan speed becomes [Low].
2. Drain pump
(1) Drain pump control
The drain pump turns ON for the specified amount of time when any of the following conditions is met:
1) ON for 3 minutes after the operation mode is switched from COOL or DRY to another operation mode (FAN).
2) ON for 6 minutes after the float switch is submerged in the water when the float switch control judges the sensor is in the water.
(2) Float switch control
Float switch control judges whether the sensor is in the air or in the water by turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
Float SW
ON
OFF
HWE08010
Hr
ON
AFTER
OFF
ERROR CODE
FUNCTION
˚F˚C
FILTER
WEEKLY
SIMPLE
AUTO OFF
ON/OFF
ON/OFF
FILTER
DAY
CHECK
TEST
OPERATION
CLEAR
Type
15sec.
15sec.
In the water
In the air
<How to operate>
1. Press POWER [ON/OFF] button.
2. Press the operation [Mode] button to display FAN.
Fan speed notch
[Low], [Med], [High], [Auto]
15sec. 1min.30sec.
In the water
Error
postponement
- 12 -
1min.30sec.
Drain pump
abnormal