EcoSystem
4
Step
Support Components

EcoSystem Bus Supply

Design Statement: The EcoSystem bus supply is required for two
or more ballasts (or BMFs) to work together. The bus supply powers
the communication bus and is capable of supporting up to 64 ballasts
or BMFs. For integration of multiple bus supplies or other lighting
control systems, please contact a Lutron Representative.
Dimensions
W: 1.77" (45mm)
H: 3.56" (85mm)
D: 3.62" (92mm)
Limits
Each EcoSystem bus can
accommodate the following:
64 Ballasts/BMFs
32 Occupancy Sensors
64 Wallstations or
Infrared Sensors
8 Daylight Sensors
|
16
Lutron
|

bus supply

EcoSystem Digital Bus Supply
CS-1L-CM (shown)
Contractor mountable, no enclosure,
2 contact closures, 1 panic contact closure
CS-1L-WM
2 contact closures, 1 panic contact closure, 1 wallstation/
IR connection, wall-mountable inside enclosure
Accepts one panic normally open or normally closed
dry contact closure to override light level to full output
EcoSystem bus may be wired Class 1 or Class 2;
bus wires are polarity insensitive
Topology-free wiring; Bus supply may be wired to the
communication bus at any point
Output voltage: 16VDC 250 mA Max (Class 1 or Class 2)
Powered by 120 or 277 V, ~50 or 60 Hz
Bus supply terminals:
- EcoSystem bus: #12 – #18 AWG (2.05 – 1.02mm) Solid
- Power wiring: #12 – #18 AWG (2.05 – 1.02mm) Solid
- Class 2 contact closures
Non-volatile (EEPROM) memory stores system programming
for 10 years from power down to power restored
Lutron recommends 1 bus supply for each room being
controlled by EcoSystem
Power draw is < 0.12 A; can be fed with same circuit as fixtures
www.lutron.com/ecosystem