Quiet Operation (Cooling Mode/Cooling Area Of Dry Mode) - Panasonic CS-E7NKDW Service Manual

Hide thumbs Also See for CS-E7NKDW:
Table of Contents

Advertisement

2
Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above
and the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control,
the vane will shift to close position.
12.4.2
Horizontal Airflow
For CS-E7/9/12/15NK, the horizontal airflow direction louver can be adjusted manually by hand.
For CS-E18NK, the horizontal airflow direction louver are as following.
1
Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within
the angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below. It does not swing during fan motor stop.
Heating, with heat exchanger temperature
Cooling and Soft Dry
2
Manual horizontal airflow direction can be set using remote control; the angles of the vane are as stated
below and the positions of the vane are as Figure 2 above.
Pattern
Airflow Direction
Patterns at Remote
Control
Vane Angle (°)

12.5 Quiet operation (Cooling Mode/Cooling area of Dry Mode)

A. Purpose
To provide quiet cooling operation compare to normal operation.
B. Control condition
a. Quiet operation start condition
When "POWERFUL/QUIET" button at remote control is pressed twice.
o
POWERFUL/QUIET LED illuminates (low intensity).
Operation Mode
1
2
90
70
52
Vane Angle (°)
A
70 ~ 110
B
90
70 ~ 110
3
4
80
100
5
110