Sanyo SGP-E70J2GU2 User Manual page 61

Table of Contents

Advertisement

Design
5Combined installation investigation
Provisional installation (calculation of distance between
units and between rows).
Here the provisional arrangement of different model
types
will be investigated (Table 1)
1)Calculation parameters (table 2)
• Outdoor unit external dimensions
U
: Height (m)
H
U
: Width (m)
W
U
: Depth (m)
D
• Outdoor unit fan air speed (table 3)
Q : Fan flow volume (m
* For installation parameters, see 3combined
installation parameters".
2)Calculation of the average distance between units La and
the distance between rows Lu.
Here provisionally La will be selected from Table 4
and next Lu calculated.
If La is large, Lu becomes small, and if La is small, Lu
becomes large.
*However, the minimum maintenance space between
units and rows shown in Table 4 must be maintained.
a) Provisional determination of La
There are 3 patterns for the arrangement in the row
direction, as follows.
(continuous arrangement up to 3 units)
La is respectively taken as follows.
3
/min)
5. Criteria for positioning the outdoor unit
[Pattern 1] Independent arrangement
D - 17
Table 1
Table 2
Table 3
Table 4