Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Quickie Rhythm

  • Page 2 ©2006 Sunrise Medical...
  • Page 3: Table Of Contents

    Acronyms for Delphi ............103 Quickie Electronics by Delphi ..........39 Hand Control Types and Functionality ......39 APPENDIX A RHYTHM 2009 WITH PG DRIVES ......0.1 QC 4 Button Joystick..........39 QC 5 Button Joystick..........39 QR3 – 3 Button Rehab Control ......40 QR7 – 7 Button Rehab Control Assignable ....
  • Page 4: Introduction

    This Service Manual has been compiled as a troubleshooting guide for the Quickie Rhythm and Groove. Photographs and content may differ from the actual products in some cases due to changes in specifi cations and other factors.
  • Page 5 INTRODUCTION QUICKIE RHYTHM Quickie Rhythm Facts • Mid Wheel Drive (MWD) • Standard 6.5 mph motor ( 300 lb. capacity) or optional 5.0 mph motor (400 lb. capacity) • Up to 3 inch obstacle Climb • Up to 8.5 mph •...
  • Page 6: Diagnostics Chart

    INTRODUCTION Diagnostics Chart Module Error Battery Operating State of Charge Indicator State Indicator Seating Indicator Controller Internal Error Drive Loss of Communication Drive Joystick is not Neutral Drive Left or Right Park Brake Drive Right Motor Open Circuit or Encoder Drive Left Motor Open Circuit or Encoder Drive...
  • Page 7: Basic Setup

    Cable from Joystick to the Bus Line Control Module; for the Groove located in the Center between the 2 batteries Control Module; for the Rhythm located at back of chair behind shroud Are all necessary connections fastened or inserted? □...
  • Page 8: Multimeter Tutorial

    INTRODUCTION Multimeter Tutorial MULTIMETER The Multimeter The multimeter is one of the most useful tools in the toolbox. It can be used to check wires, shorts, voltages, resistance, all manner of electrical circuits. This tutorial is designed to help clarify the symbols and socket op- tions found on various multimeters.
  • Page 9: Symbols

    INTRODUCTION Symbols This section describes the basic symbols used in a typical multimeter. This symbol means alternating current. Use this when you want to test something that has AC current running through it. Typically you’d want to test the voltage of an inverter (for cold cathodes or neons) or a similar device. This means Direct Current.
  • Page 10: Health And Safety

    INTRODUCTION Health and Safety Good Working Practices While working on powered mobility products, it is essential to observe good working practices. Below are a series of safety guidelines and recommendations. Please note that these precautions are intended to serve only as a guide, not to supersede or replace any safety statute, NHS or other safety regulations.
  • Page 11: Battery Chargers

    INTRODUCTION • Remove personal items of jewelry, such as rings, watches, chains etc. before working on batteries. Such items could cause short circuits resulting in serious burns. • Batteries are constructed of heavy materials. Therefore moving batteries requires appropriate lifting techniques. Safety footwear should also be worn. In addition, disposal of old batteries requires correct procedures.
  • Page 12 INTRODUCTION Sources of EMI 1. Hand-Held Transceivers: The antenna is usually mounted directly on the unit. These include: • Citizens band (CB) radios • “Walkie-talkies” • Security, fi re and police radios • Cellular phones • Lap top computers with phone or fax •...
  • Page 13: Electro Static Discharge

    INTRODUCTION Electro Static Discharge To help prevent Electro Static Discharge (ESD) the following proper handling techniques should be followed: ESD: • Do not place Printed Circuit Boards or their containers near sources of strong electrical fi elds (such as above a CRT). •...
  • Page 14 INTRODUCTION ©2006 Sunrise Medical...
  • Page 15: Power Base Section

    POWER BASE SECTION Rhythm & Groove Power Bases Batteries Safety If mishandled batteries can be dangerous and hazardous. • All mobility batteries, whether wet type or gel/sealed type, contain lead and sulfuric acid. Both of these materials are toxic and in the case of sulfuric acid, highly corrosive.
  • Page 16: Battery Diagnostics

    POWER BASE SECTION Battery Diagnostics How Long Should Batteries Last? An average of 1 to 1.5 years. Factors that affect battery performance: • Maintenance - Poor maintenance. • Charging - Improper charging shortens battery life. • Chair Components - Malfunctioning electronics, bad motors, electric brakes, and corroded wiring are just some of the factors that may affect battery life and performance.
  • Page 17: Battery Types

    • Only use Deep-Cycle sealed type batteries in a wheelchair. 22 NF Batteries Used On both Groove and Rhythm Battery Size • Batteries function as a power wheelchair’s fuel tank. The larger the group size, the farther the wheelchair will go.
  • Page 18: Accessing The Batteries

    POWER BASE SECTION Accessing the Batteries Rhythm Rhythm Unscrew each of the 2 Seat Studs (A) until they release. Carefully tilt Seat Assembly back until it stops. Lift the front of Battery Cover Panel and pull it forward to expose the batteries.
  • Page 19: Changing The Battery

    POWER BASE SECTION Changing the Battery Rhythm Rhythm Firmly grasp the red battery connectors and pull apart. Firmly grasp the black battery connectors and pull apart. Firmly grasp the smaller white battery connectors and pull apart. Using provided strap, carefully lift battery from chair.
  • Page 20: Battery Connectors

    POWER BASE SECTION Battery Connectors The battery connection uses a 2 way connector with a White Jumper to give the series connection of 24 volt It has a clearly designated RED and BLACK connector which connect to the Positive for RED and the Nega- tive for the BLACK with JUMPER (White) joining the system.
  • Page 21: Battery Chargers

    POWER BASE SECTION Battery Chargers Chargers and Charging • Use the wheelchair manufacturer’s automatic charger for all routine charging. • The best recharge point for deep cycle batteries is roughly at 50% discharge. • Never run batteries completely fl at [total discharge]. •...
  • Page 22: Lightweight Charger

    POWER BASE SECTION Lightweight Charger The Lightweight Charger is a switched mode 8 amp output charger. Because of its compact size it uses a forced air cooling system. After the voltage drops to 25.7 volts, the charger will come back on at a lower Amp range of 2 amps to recycle the batteries.
  • Page 23: Motors

    POWER BASE SECTION Motors Checking Motor Resistance and Continuity Motor Connector Motor Motor Brake Solenoid Resistance Resistance Brake Solenoid Standard 0-2 ohms 21.0-22.0 ohms Motor Encoder 0-2 ohms 15.0-17.0 ohms Fig 1.18 Fig 1.20 Fig 1.19 Checking the Motor Brushes Note: When removing brushes from the motor for Brush Assembly inspection, please note orientation and location of the...
  • Page 24: Hubs And Bolts

    POWER BASE SECTION Hubs and Bolts Rhythm Groove Fig 1.25 Fig 1.26 Use a 19mm wrench to remove the nut off of end of shaft. Take the washer away. Use a pulley puller to remove the Hub Assembly from the output shaft. (Fig 1.25&1.26) Note: Do not lose the hub assembly locating woodruff key.
  • Page 25: Motor Removal And Replacement Rhythm

    POWER BASE SECTION Motor Removal and Replacement Rhythm Raise the chassis of the chair on a stable platform so that all wheels are off of the working surface. Lift the center pad of the fasteners that secure the side shroud to the chair. Remove the fasteners (fi g 1.29) and after disengaging the side shroud from the front shroud, remove the side shroud and set aside.
  • Page 26: Motor Removal And Replacement Groove

    POWER BASE SECTION Motor Removal and Replacement Groove Support the Groove power base securely using jackstand or suitable blocking. Remove the drive wheel lug nuts using a 16mm Socket wrench. Set Drive wheel aside (fi g 1.33). Fig 1.33 Remove the Cotter Pin from the Freewheel Mechanism and discard the cotter pin (fi...
  • Page 27: The Freewheel Mechanism

    16-20 Newton Meters (12-15 ft-lbs). Torque drive wheel lug nuts to 47.5-54 Newton Meters (35-40ft-lbs). Note: Always use new cotter pins. Fig 1.38 The Freewheel Mechanism Rhythm Free Wheel Assembly Free Wheeling Engaged Fig 1.39 Fig 1.39 ©2006 Sunrise Medical...
  • Page 28 POWER BASE SECTION Groove Free Wheel Assembly Push in - Rotate down Engaged Free Wheeling Fig 1.42 Fig 1.40 Fig 1.41 COMPENSATOR ASSEMBLY ROD FASTENING NUT BALL JOINT ROD END COG RELEASE ROD 5 3/4” 1 1/4” 3/8” 12” 8 THREAD ENGAGEMENT 7/16”...
  • Page 29: Drive Wheels

    POWER BASE SECTION Drive Wheels Changing Drive Wheel Assembly Disassemble: Carefully support the frame of the wheelchair us- ing jack stands. Remove the four lug nuts using a 16 mm socket wrench. Slide Wheel assembly off Hub. Reassemble: Align wheel and slide back onto hub. Replace the four lug nuts and tighten to 35-40 ft.
  • Page 30 POWER BASE SECTION Motor Encoders Introduction Encoders allow chairs maintain a straight line while driving on uneven terrain and allows the usage of Switch Controls without the normal veering of other products. It does this by 5 individual Hall Effect Sensors that will detect 1 degree per 360 degree rotation of the wheel by means of the Encoder.
  • Page 31 POWER BASE SECTION Final Step is to Plug in Programmer Go to Program (Fig 1.50) Go to Motor control (Fig 1.51) Go into General Parameters (Fig 1.52) Go into General – which is Encoder Selection – Using On for operation Set Encoder to: On (enable) (Fig 1.53)–...
  • Page 32: Suspension

    POWER BASE SECTION Suspension The Quickie Rhythm base has a special 4-bar suspension system that pulls the front caster wheels up over curbs, while simultaneously maintaining independent suspension on the remaining four wheels. • The front caster housing pivots horizontally, which absorbs front impact.
  • Page 33 Note: Contact Technical Service for any changes to the seating system such as addition of Tilt, Lift, or Ventilator. Fig 1.58 Dampening assembly Rhythm Fig 1.59 ©2006 Sunrise Medical...
  • Page 34: Anti-Pitch Timing Adjustment

    For Rhythm, each rear suspension element controls the pitch damper mechanism on that side of the chair. Timing of the initiation of the anti-pitch function on the Rhythm can be accomplished by the following method. • Place the chair on a pedestal so that the drive wheels are suspended off of the riding or work surface.
  • Page 35 POWER BASE SECTION • Adjusting the timing of the anti-pitch effect is Cable Attach & Adjust accomplished by rotating the nut at the end of the anti-pitch actuation cable at the anti-pitch housing. The anti-pitch housing is located on the stainless steel anti-pitch shaft inboard of the drive motor.
  • Page 36: Anti-Pitch Damper Mechanism Cleaning

    POWER BASE SECTION Anti-pitch Damper Mechanism Cleaning If the Anti-Pitch Mechanism becomes contaminated with grease or oil it will be necessary to remove and disassemble it for cleaning. • Raise the chassis of the chair on a stable platform, such as jack stands, so that all wheels are off of the working surface.
  • Page 37 POWER BASE SECTION Using a soft hammer tap down on the top of the cylin- der to release the internal parts. Fig 1.68 Use soap and water, alcohol or acetone to clean the Damper Rod and the plastic Anti-Pitch Taper. Do not lubricate any parts of the anti-Pitch Assembly.
  • Page 38: Replacing Shrouds

    POWER BASE SECTION Replacing Shrouds Rhythm • The Front (B) and Side shrouds (A) are held in place by reusable shroud fasteners (C & Fig 1.71). • To remove the fasteners, insert a fl at blade screw driver under the slot of the fastener center piece and pry up.
  • Page 39: Quickie Electronics Section

    QUICKIE ELECTRONICS SECTION Quickie Electronics by Delphi Hand Control Types and Functionality Joystick Descriptions: QC 4 Button Joystick • All joysticks use a Centered Power On/Off Sunrise P/N 101568 or 104972 button which have a delay for Power-up Power – On/Off •...
  • Page 40: Qr3 - 3 Button Rehab Control

    – each 7 button hand control w/ toggle assignable button can be programmed for two switch for mode and speed pot distinct functions using either HHP or Quickie iQ Fig 2.4.2 replacement (Fig.2.4.3 shows using Quickie iQ to program...
  • Page 41 QUICKIE ELECTRONICS SECTION Fig 2.4.3 Drive Profi le Mode Red Mode light Shows fl ashing and Choice of Drive can be made There are 4 separate Drive Profi les to choose. After depression of Mode Button push in any of the 4 direc- tions to choose what Drive Profi...
  • Page 42 QUICKIE ELECTRONICS SECTION Hand Control Parts Replacement Flying Lead Replacement Remove the Joystick from the Joystick Mount Remove the four T 10 torx screws from the bottom case of the Joystick (fi g 2.7.1) Remove the bottom case Remove the strain relief from the bottom case...
  • Page 43 QUICKIE ELECTRONICS SECTION Joystick Housing Replacement Turn off Joystick and unplug Remove the Joystick from the Joystick Mount Remove the four T 10 torx screws from the bottom case of the Joystick (fi g 2.7.1) Remove the bottom case If bottom case is equi-...
  • Page 44 QUICKIE ELECTRONICS SECTION Additional Hand Control Heels and add-ons Heels are exchangeable by removing the 4 Torx screws and separating the heel from the main body of the hand control. Disconnect the cable from the heel to the main body of the control (where applicable), and ensure that Fig 2.10.1...
  • Page 45 QUICKIE ELECTRONICS SECTION Wiring • Before making any connections to the Hand Control, disable the Wheelchair by disconnecting the Batteries and/or elevating the drive wheels. • Use only Sunrise Medical approved wiring Harnesses to connect the Hand Control. • Wiring should be suitably restrained and fastened to the wheelchair to prevent snagging and to Fig 2.12...
  • Page 46 QUICKIE ELECTRONICS SECTION Programmable Ranges Menu Item Description Range Drive Profi les Determines number of profi les (QC=1 QR=4) Device Selects Drive input when profi le is Active Forward Speed Determines Fwd Speed settings 5 - 100 Reverse Speed Determines Rev Speed settings 0 –...
  • Page 47 QUICKIE ELECTRONICS SECTION Power On / Off Options This button turns the wheelchair control on and off. You can see if the wheelchair control is on by looking at the lights just under the on/off button. If any of the lights are visible, the control is on.
  • Page 48: Programming Devices

    QUICKIE ELECTRONICS SECTION Programming Devices Hand Held Programmer Hand Held Programmer Features : • (+) and (-) keys (A) to increase or decrease data • Up, Down, Left, and Right key (B) Moves around in the menu • The top three buttons are reserved for future •...
  • Page 49 QUICKIE ELECTRONICS SECTION FULL QR MOTOR CONTROLLER (QR-ACT) QR-ACT – Rehab Motor Controller w/ Actuator Out- SUNRISE PART # 020001 puts • Accepts Motor Encoders for Intellidrive option. • Works with Attendant Control • Accepts two external switch inputs, which can be used for external seat reversal switch, Drive inhibits or 1/2 Direct Actuator Control Switches.
  • Page 50 QUICKIE ELECTRONICS SECTION QR-MAC - Quickie Rehab Multiple Actuator Control SUNRISE PART # 020007 Works only with QR system. • Used when more than 2 actuators are required in the seating system. • Actuator outputs for left and right leg rests (4A), tilt, lift, recline (10A).
  • Page 51: Electronic Pin Out Characteristics - Qc Motor Controls

    QUICKIE ELECTRONICS SECTION Electronic Pin Out Characteristics – QC Motor Controls Direct Switch Pin Outs Can Bus Pin Outs Pin Defi nition Defi nition Actuator Pin Outs No connection CAN Hi Defi nition Ground CAN Lo Actuator + Switch 1...
  • Page 52: Electronic Pin Out Characteristics - Qr Motor Controls

    QUICKIE ELECTRONICS SECTION Electronic Pin Out Characteristics – QR Motor Controls Analog Sensor Pin Outs Actuator Pin Outs Defi nition Defi nition +24V Actuator + Ground Switch A (Encoder A or Reed or Limit) Analog 1 Ground Analog 2 Switch B (Encoder B or Limit)
  • Page 53: Diagnostics Overview

    Error Description Priority * Refer to the following tables for a quick diagnostic Motor Controller Internal guide provided by the Battery Gauge on the Quickie Module Error system.For additional information, refer to the Users Module Communication Error guide for each system.
  • Page 54 QUICKIE ELECTRONICS SECTION Seating Mode Errors Errors are indicated by the LED associated with the Mode Button Flashing GREEN. LED illumination state Error Description Priority * Actuator Internal Error Module Communication Error 3 Actuator Hex Switch not Neutral at Power On...
  • Page 55: Delphi Diagnostics Trouble Shooting Chart

    QUICKIE ELECTRONICS SECTION Delphi Diagnostics Trouble Shooting Chart Symptom Code Flash Diagnosis Solution Battery Voltage has 1 Bar – every 2 seconds Batteries Depleted Recharge batteries Dropped Lower or Raised Loose or Disconnected Test with Volt Meter Higher Than Operating...
  • Page 56 QUICKIE ELECTRONICS SECTION Fault Isolation Procedures Using Quickie iQ or Hand Held Programmer Introduction Observe all safety precautions in the Quickie iQ, the HHP Owner’s Manual and the Rhythm and Groove Technical Service Manual. Connect the Quickie iQ or the HHP to the wheel-...
  • Page 57 Battery Tests Perform the following steps to check the initial state-of- charge and to load test the Batteries. Connect the Quickie iQ or HHP to the wheel- chair. Warning If the following step is not completed the wheel- Fig 2.23.5...
  • Page 58 Run the chair for a few minutes to partially dis- charge the batteries. Battery + + - Connect either the HHP or the Quickie iQ to the Battery Votage 24.8 wheelchair. Battery SOC Turn on the wheelchair.
  • Page 59 Connect the battery charger to the wheelchair. Connect the battery charger to an outlet. Observe the battery voltage on either the HHP or Quickie iQ. Refer to the following notes: • The battery voltage should slowly increase from its starting value once the charger is connected.
  • Page 60 The Motor Current should be even for both motors when the Motor Voltages are equal. A typical value for the Rhythm or Groove motors with the gear box disengaged is 4 to 6 amps. Cold motors may indicate higher current.
  • Page 61 Operate the wheelchair by moving the joystick slight forward. Observe the Brake Current and Brake Voltage. • The Rhythm and Groove use 12 VDC park brakes. Typical Brake Voltage is 11 VDC. • The Brake Current should be approximately 0.5 amps. Typical values are between 0.4 amps and 0.6 amps.
  • Page 62 Drive Control Tests Hand Control Test Complete the following steps to test the Hand Control Connect the Quickie iQ or HHP to the wheel- chair. Warning If the following step is not completed the wheelchair may move unexpectedly possibly causing injury.
  • Page 63 QUICKIE ELECTRONICS SECTION If using the Quickie iQ, select Monitor Parameter followed by selecting Hand Control, then JS Position. (fi g 2.23.18) Fig 2.23.17 Slowly move the joystick forward and verify that the Joystick Position increases smoothly to 100%. Repeat the test in the reverse direction.
  • Page 64 Operate each button (or toggle switch) one at a time to verify that they function correctly. This is indicated on the HHP by the box highlighting. On the Quickie iQ, the status will change from Open to Closed. Note, allow a few seconds for the system to respond.
  • Page 65 Quickie iQ by the status changing from Open to Closed. If using the HHP, select S&P Pressure for Sip and Puff test. If using the Quickie iQ, select Sip and Puff Pres- sure.
  • Page 66 QUICKIE ELECTRONICS SECTION Actuator Test (Motor Controller controlled actua- tors) Complete the following steps to test the seating system actuators. Connect the Quickie iQ or HHP to the wheel- chair. Tilt Turn on the wheelchair. Prior to completing any + + - test, re-home the wheelchair.
  • Page 67 Verify that the actuator travels to the count programmed in the chair. Refer to the following notes: • If using Quickie iQ, this value may be found under Programmed Parameters Access, Motor Control, then Actuator 1 or 2. (fi g 2.23.24) Fig 2.23.24...
  • Page 68 Actuator Test (QMAC controlled actuators) Complete the following steps to test the seating system actuators. Connect the Quickie iQ or HHP to the wheel- chair. Turn on the wheelchair. Prior to completing any test, re-home the wheelchair using either the HHP or the PCSS.
  • Page 69 Recline tuator under test (i.e. Recline). (fi g 2.23.28) + + - Enable • If using Quickie iQ, this value may be found un- Input Dir Swap Speed der Programmed Parameters Access, QMAC, Accel and then select the actuator under test (i.e.
  • Page 70 General Wheelchair Test Complete the following test to verify Time On, Time Driven, and Internal Control Box Temperature (Motor Controller). Connect the Quickie iQ or HHP to the wheel- chair. Turn on the wheelchair If using the HHP, select Monitor, then System,...
  • Page 71: Seating

    SEATING Perfect Fit Seating System Introduction The integrated Perfect Fit Seating System is available in both non-recline, and recline with shear reduction. The Perfect Fit Seating System is designed to adapt to various platforms, including front, rear, and mid-wheel bases using either a fi...
  • Page 72 SEATING SECTION The Posterior Lateral Positioning Back contains: • Deeply curved lateral wings to provide a lateral • Headrest adjustment points • Up to 7” width adjustment • Up to 3” height adjustment • Posterior lateral support (135 mm) Fig 3.4 The curved General Purpose Back contains: •...
  • Page 73 SEATING SECTION The Power Recline with Shear Reduction provides: • Shear induced during full angle range: 2” to 2.5” • Back reclines from vertical (95°)to full recline (171°) Fig 3.7 Fig 3.8 Changing the Seating Size Changing the seating size of the Perfect Fit Seating System is accomplished by either adjusting the width, depth, and/or the back height by relocating the growth pans;...
  • Page 74: Adjustments

    SEATING SECTION Adjustments Refer to the following tables for the range of adjustments for the Perfect Fit Seating System. Seat Pan Width Table Narrow Center Medium Center Wide Center 12” – 17” 15” – 20” 19” – 24” Seat Pan Width Front of Chair Fig 3.12 Seat Frame Depth Table...
  • Page 75: Seat Back And Seat Pan Width Adjustments

    SEATING SECTION Manual Recline Back Height Table Wing Back Height Bottom of Back from Seat Pan 15” 15.5” – 18.5” .8” – 3.8” 17” 17” – 20” .5” – 3.5” 19” 19” – 22” .5” – 3.5” Seat Back 21” 21”...
  • Page 76: Seat Back Height Adjustments

    SEATING SECTION Seat Back Height Adjustments Note: Each starting back height adjusts upward 3”. The adjustment is based on a slot & block alignment. Refer to the following illustrations for adjustment procedures and ranges. • Remove back cushion. • Locate the mounting hardware securing the back assembly to the Perfect Fit Seating System.
  • Page 77: Seat Depth Adjustments

    SEATING SECTION Seat Depth Adjustments The seat has 3” to 4” of built in depth adjustment depending on the starting depth. Note: Seat Depth Adjustment is only used as a means of accommodating an offset backrest. To adjust the seat depth, follow these adjustments: •...
  • Page 78: Manual Back Rest Adjustment

    SEATING SECTION Manual Back Rest Adjustment Two versions of the manual back adjustment are available, the Adjustable Integrated Back and the Manual Recline to 40 Degree Back. To adjust the Adjustable Integrated Back, complete the following procedures: • Locate the 16 mm adjusting nut on the rear bottom of the back.
  • Page 79: Arm Rest Adjustments

    SEATING SECTION Arm Rest Adjustments 1. The Perfect Fit Flip Back Height Adjustable Armrest is only available with the manually reclining backrest. 2. Armrest height ranges from 7”–14”. Up to 2” of width adjustment is available. Complete the following procedures to adjust the armrest height: To adjust the armrest height, loosen the two mounting-clamp bolts(A), slide the armrest up or down and retighten.
  • Page 80 SEATING SECTION Level the Arm Pad Complete the following steps to level the arm pad: • Loosen the upper clamps. • Pull the armrest out. • Reinsert the armrest so the arm pad is parallel to the ground and tighten the upper clamps. Notes: This method of adjusting the armrest height adds an additional 2”...
  • Page 81: Armrest Angle Adjustment

    SEATING SECTION Armrest Angle Adjustment Complete the following procedures to adjust the angle of the armrest. Loosen the outer clamp. (A) Turn the rear, fi ne-tune adjustment screw (B) in the upper armrest adjustment clamp clockwise or counter clockwise, depending on the change needed.
  • Page 82: Installation - Adjustment Of Lateral Knee Supports

    SEATING SECTION Installation - Adjustment of Lateral Knee Supports Standard Mounting • Mount and Adjust Lateral Knee Supports using the two mounting screws (Fig 3.37 & Fig 3.38). • To open Lateral Knee Supports, push release Mounting Screws lever and rotate out (Fig 3.39). •...
  • Page 83: Leg Rest Hangers

    SEATING SECTION Leg Rest Hangers New leg rest hangers are used on the Perfect Fit Seating System. These hangers provide more positive lock. The following drawing illustrates the repair/ adjustment procedures: • Locate the adjustment bolt covered with a rubber bumper (A). •...
  • Page 84: Installing And Adjusting Side Guards

    SEATING SECTION Installing and Adjusting Side Guards • Mount the side guard on the seat pan rail as illustrated. • Slide the side guard forward or rearward as required. • Adjust the height of the guard by moving up or down the guard plate.
  • Page 85: Mounting And Adjust Head Rests

    SEATING SECTION Mounting and Adjust Head Rests • Head rests come in different styles. Several third party head rests such as Whitmyer, Otto Bock and Jay may be used. • Mount them to the seat back mount as illustrated. • Adjust the head rest by sliding it up and down, as well as rotating it in its mount.
  • Page 86: The Perfect Fit System

    SEATING SECTION The Perfect Fit System Theory of Operation The Recline Portion of the Perfect Fit Seating System uses dual keipers to operate the back. Each keiper is powered by independent 24 VDC motors. A cogged belt connects the motors to the keipers. The keipers are similar to those used in the automobile industry to recline seat backs.
  • Page 87 SEATING SECTION The PC board has several functions, including routing the voltage from the controller module to the recline actuators. The optical encoder sends its signal to the PC board. The PC board routes this signal to the control module where it is analyzed for correct Encoder Reset Switch operation and position.
  • Page 88: Troubleshooting The Recline Seating System - Without Qr-Mac

    SEATING SECTION Troubleshooting the Recline Seating System - without QR-MAC Prior to troubleshooting the Perfect Fit seating system, verify that the QR-MAC is correctly programmed and that the actuators are enabled. Refer to the HHP Ground Owners Manual. See below to troubleshoot each indicated fault. The Recline Actuator will not function or will not correctly function.
  • Page 89 SEATING SECTION If the readings are not in the acceptable range (3 to 9 ohms), replace the keiper assembly and retest. Locate the Encoder Reset and Back EOT and Home EOT switch assembly on the back of the chair. Locate the two EOT switches at the bottom of the mounting plate.
  • Page 90 SEATING SECTION The chair will not drive or will only drive in creep mode Verify that the battery charger is not plugged into the chair. Verify that there are no faults displayed on the joystick or Enhanced Display. If faults are displayed, refer to the Delphi troubleshooting section of the service manual.
  • Page 91: Trouble Shooting Seating Function Other Than Recline

    Locate the control module on the wheelchair. Note: The control module is located at the rear of the base on a Rhythm and between the batteries on a Groove. Verify the connector leading to the suspect actuator is mated to the control module.
  • Page 92: Troubleshooting The Perfect Fit System With Qr-Mac

    SEATING SECTION If any reading is not correct, disconnect each cable at the actuator and check for continuity through it to the control module. Replace any defective cable and retest. If the readings are correct, replace the control module and retest. If replacing the control module does not correct the problem, replace the appropriate actuator or seating component and retest.
  • Page 93 SEATING SECTION Verify that the BUS cables leading to the seating system are mated at the back of the wheelchair. If disconnected, reconnect and retest. Fig 3.64 Check for battery voltage at the 2-pin connector leading to the QR-MAC If battery voltage is present at the 2-pin connector and no seating functions are illuminated, replace the QR-MAC and retest.
  • Page 94 SEATING SECTION Disconnect the 2-pin connector and measure for battery voltage on the cable leading to the base. If battery voltage is not present at the 2-pin connector, verify that the 15-amp fuse in the base of the wheelchair is not defective and that the 2-pin connector near the batteries is mated correctly.
  • Page 95 SEATING SECTION Individual Actuators Do Not Function or Function Correctly Verify that the seating functions illuminate on the input device (joystick or Enhanced Display). If not, or if any fault codes are displayed, refer to the Delphi troubleshooting section of the service manual. Locate the QR-MAC on the rear of the wheelchair Fig 3.70...
  • Page 96 SEATING SECTION Actuator Approximate Reading In Mid- Approximate Reading at Stroke Home Position Left Leg (for powered foot 4 ohms 2 meg ohms or greater platforms) Left Leg or Right Leg (for 8 ohms 2 meg ohms or greater independent legs Tilt 2 ohms 2 ohms...
  • Page 97 SEATING SECTION Verify correct operation of the 18-degree reset Motor Armature – switch by checking its operation at the 6-pin approximately 5 ohms. connector. Refer to the following drawing for the correct readings. Switch pressed – Open Switch not pressed – Closed Replace the 18-degree reset switch assembly if defective and retest.
  • Page 98: Reed Switch Adjustment

    SEATING SECTION Reed Switch Adjustment With the back pan set at 95° ±1° with respect Rocker Switch to the seat pan, the Actuator Magnet (B) should activate Reed Switch “A”. Actuator Magnet (B) may be moved vertically as shown by arrow (C) to accomplish this set up. Actuator Rocker Switch MUST be in the down position as Bracket...
  • Page 99: Power Modules

    SEATING SECTION Power Modules Tilt System • 50 degrees of tilt. • Linak Actuator. Fig 3.80 Fig 3.79 Pin 1 Motor + Brown Pin 2 Encoder Pin 3 Ground Black Pin 4 COT Switch Pin 5 Motor - Blue Pin 6 24 Volt Switched Power Fig 3.81 •...
  • Page 100 SEATING SECTION Power Modules Lift System • Eleven inches of lift. • Linak Actuator. • Cross arm x-style actuation design. • Connects directly to the motor controller. • Operated by either a toggle activation switch or directly through the joystick. Fig 3.84 Pin 1 Motor +...
  • Page 101: Seat Interface

    SEATING SECTION Seat Interface Permanent Tilt Adjustments The Perfect Fit Seating System may be mounted with 0, 3, 6 or 9 degrees of permanent tilt. The system uses a fi ller plate to mount the seat to the base. The tilt angle may be adjusted as follows: Remove the adjustment bracket (B) by removing the mounting hardware.
  • Page 102: Power Recline With Power Shear Reduction

    Tilt or Recline, the wheelchair reverts to a programmable Creep Profi le. This profi le may be modifi ed by either the HHP or Quickie iQ to run slower than the factory settings. Creep speed is a percent of maximum Creep speed programmed by Sunrise Medical.
  • Page 103: The Wheelchair Will Only Drive In Creep Speed, Or The Back Will Not Drive To The Preprogrammed Value

    SEATING SECTION The wheelchair will only drive in Creep Speed, or the back will not drive to the preprogrammed value Locate the Recline Counter Reset Switch (CRS) Fig 3.90 mounted on the left seat hinge (Fig 9.90). Note: this switch is Normally Open (NO) when the seat is fully elevated, and closes as the seat-back reclines.
  • Page 104 SEATING SECTION Connect a meter to the 2 pins indicated in the Fig 3.93 photo (Fig 3.93). Check continuity through the switch by pressing in on the Recline CRS plunger. Note, when the seat-back is in the full upright position the switch should open.
  • Page 105: The Back Will Not Drive To The Preprogrammed Shear Value

    SEATING SECTION The back will not drive to the preprogrammed shear value Additionally there may be encoder errors. Use the Fig 3.96 HHP to re-home the chair prior to completing any tests. Complete the following procedures to test the Shear Count Reset Switch (CRS).
  • Page 106 SEATING SECTION Connect a meter to the 2 pins indicated in the Fig 3.99 photo (Fig 3.99). Check continuity through the switch by pressing in on the CRS plunger. Note, when the seat-back is in the full up position the switch should be open. When the seat lowers the switch should close.
  • Page 107: The Recline Actuator Will Not Run, Or Runs Erratically

    To test the current drain and operation of the en- coder switches of the Recline actuator, complete the Fault Isolation Procedures Using Quickie iQ or HHP located in this manual. Replace the Recline actuator if the procedure fails. To continue testing, complete the following procedures.
  • Page 108: The Shear Actuator Will Not Run, Or Runs Erratically

    To test the current drain and operation of the encoder switches of the Shear actuator, complete the Fault Isolation Procedures Using Quickie iQ or HHP. Replace the shear actuator if the procedure fails. To continue testing, complete the following procedures.
  • Page 109 SEATING SECTION Check armature resistance through the pins indi- Fig 3.107 cated in the photo (Fig 3.107). Nominal resistance is 6 to 8 ohms when the actuator is in mid-stroke and greater than 1 MΩ when at either extremity. If the resistance is open, follow the cable to an- Fig 3.108 other cable leading to the actuator.
  • Page 110: Adjustments

    Adjustments of the New Recline for the seat-pan are Fig 3.109 similar to the old Perfect Fit Recline. Refer to that por- tion of the Rhythm and Groove Tech Service Manual for those procedures. Adjustments for the seat-back are simpler than the old Perfect Fit Seating System.
  • Page 111 SEATING SECTION Seat-back depth is adjusted by moving the mount- Fig 3.112 ing brackets to the front or rear in the seat-pan track. Loosen the two mounting bolts (C) and slide the bracket to the desired location (Fig 3.112). To adjust the arm rest hanger, loosen the two Fig 3.113 mounting bolts (D) and slide the mount to the desired location (Fig 3.113).
  • Page 112: Recline Actuator Removal

    SEATING SECTION Recline Actuator Removal In order to remove either the recline or the shear actua- Fig 3.115 tor, the gas strut must be removed. In addition, the QR- MAC mount must be removed. Complete the following procedures to remove and replace the recline actuator. Remove the rear shroud by using a fl...
  • Page 113 SEATING SECTION Once both screws are loosened, lift the QR-MAC Fig 3.118 mount up and place it to the side (Fig 3.18). WARNING During the next steps, you will be removing the Gas Strut. It is under pressure. Be sure to use caution when removing the Recline Actuator from the chair.
  • Page 114 SEATING SECTION Use a ¼” Hex wrench and a 9/16” open-end Fig 3.122 wrench and remove the top bolt that holds the Re- cline actuator to the back structure (Fig 3.122). Unplug the three connectors to the recline actua- Fig 3.123 tor (two spade connectors (G) with red and green wires, and one 6-pin connector (H)) (Fig 3.123).
  • Page 115: Shear Actuator Removal

    SEATING SECTION Shear Actuator Removal Shear Actuator Removal Fig 3.125 In order to remove the Shear Actuator, the Gas Strut and Recline Actuator must be removed. Refer to the Recline Actuator Removal section in this tech manual. Once the Recline Actuator is removed, complete the following steps to remove the shear actuator.
  • Page 116: Recline Crs Replacement

    SEATING SECTION Recline CRS Replacement In order to eliminate the re-home switch (previously Fig 3.127 found on the Smart Seat), a separate Counter Reset Switch (CRS) is installed that allows the system to “re- home” during normal operation. This switch is located on the left side of the wheelchair next to the Recline pivot point (Fig 3.127).
  • Page 117: Shear Crs Replacement And Adjustment

    SEATING SECTION Shear CRS Replacement and Adjustment In order to eliminate the re-home switch (previously Fig 3.130 found on the Smart Seat), a separate Counter Reset Switch (CRS) is installed that allows the system to “re- home” during normal operation. This switch is located near the bottom of the shear actuator (Fig 3.130).
  • Page 118: Acronyms For Delphi

    APPENDIX A SEATING SECTION Acronyms for Delphi Acronym or Term Defi nition Attendant Control Module BSOC Battery State Of Charge Controller Area Network Customer Requirements Document Direct Current Environmental Control Module Enhanced Display Graphical User Interface Hand Control Module Hand Held Programmer Infra Red Light Emitting Diode Liquid Crystal Display...
  • Page 119 2009 Quickie Rhythm Service Manual Supplement PG DRIVES TECHNOLOGY ©2009 Sunrise Medical Inc. xxxxxx Rev A...
  • Page 120 Quickie Rhythm Service Manual Contents SEATING SECTION VR2 Remote Controller ........0.3 Section 5 VR2 Plugs/Connectors ........0.4 R-net Fault Codes ...........5.1 VR2 -Main Wiring Diagrams ......0.5 Power Chair Displays a Fault on the Hand Con- R-NET Remote Controller .......0.7 trol or Omni ............5.1 R-NET Optional Electronics ......0.9...
  • Page 121: Vr2 Remote Controller

    LED’s, which display speed and profile settings Speed/ Profile Decrease. Used Speed/ Profile Increase. Used to decrease the Speed/ Profile to Increase the Speed/ Profile setting. setting. PAGE 0.3 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL ©2006 Sunrise Medical...
  • Page 122: Vr2 Plugs/Connectors

    M1 = RIGHT SIDE MOTOR M2 = LEFT SIDE MOTOR JSM = JOYSTICK MODULE INH-2 = INHIBIT 2 A1 = ACTUATOR 1 A2 =ACTUATOR 2 OBC = ON BOARD CHARGER (not used) + - =BATTERY SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.4...
  • Page 123: Vr2 -Main Wiring Diagrams

    Motor Motor 2-way 2-way Drive POWER HARNESS Drive SB50 SB50 Left Right Black Fuse Fuse Wiring Harness Bus Harness Black Black Connector Optional Component Battery Battery PG Drives Component Third Party Component PAGE 0.5 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 124: Sunrise Medical

    2-way Drive POWER HARNESS Drive Dual-Toggle SB50 SB50 Left Dual-Toggle 3.5 mm Stereo Right DUAL-TOGGLE 4-Way Amp Single Actuator Black Phone Jack Switch HARNESS Mate-N-Loc Driver Fuse Fuse Black Black Battery Battery SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.6...
  • Page 125: R-Net Remote Controller

    Controller. Horn Key- Activates a warning horn. Speed/ Profile Decrease. Used to decrease the Speed/ Profile Speed/ Profile Increase. Used setting. to Increase the Speed/ Profile setting. PAGE 0.7 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 126 Controller. Horn Key- Activates a warning horn. Speed/ Profile Increase. Used Speed/ Profile Decrease. Used to Increase the Speed/ Profile to decrease the Speed/ Profile setting. setting. SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.8...
  • Page 127: R-Net Optional Electronics

    R-NET Optional Electronics R-net Omni R-net ISM (Intelligent Seating Module) R-net Attendant Control R-net Output Module R-net Power Module R-net Blue Tooth Module PAGE 0.9 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 128: R-Net Plugs/Connectors

    M1 = RIGHT SIDE MOTOR M2 = LEFT SIDE MOTOR JSM = JOYSTICK MODULE INH-2 = INHIBIT 2 A1 = ACTUATOR 1 A2 =ACTUATOR 2 OBC = ON BOARD CHARGER + - =BATTERY SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.10...
  • Page 129 2. Reverse Jack ISM (Intelligent Seating Module) 3. Left 4. Right Actuator 5. Speed Down Channels Left Inhibit 6. Speed UP Lights 7. Horn 8. Common 9. NC Inhibit Right Lights Actuator Channels PAGE 0.11 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 130: Main Wiring Diagram R-Net

    Intech Intech Battery Intech Motor Motor Switch 2-way 2-way Drive Drive POWER SB50 SB50 Left HARNESS Right 6-Way Black Seat Tilt Mini-Fit J r. Fuse Fuse ACTUATOR HARNESS Black Black Battery Battery SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.12...
  • Page 131 POWER 2-Way PGD SB50 SB50 Inhibit4 Left Inhibit HARNESS Right 6-Way Black Seat-back 2-Way PGD Seat Tilt Inhibit5 Mini-Fit J r. Inhibit angle switch Fuse Fuse ACTUATOR HARNESS Black Black Battery Battery PAGE 0.13 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 132 SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 0.14...
  • Page 133: Battery Connection Test

    If the voltage meter reads zero at the motor controller, then measure the battery harness connector as shown in (fi gure 1.1.3). If the voltage meter reads full voltage at the battery harness, then replace the Motor Controller. 1.1.3 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 1.1...
  • Page 134: Check Battery Wire Harness

    + terminal and the black lead on the negative terminal as shown in (figure 1.2.1). If the polarity is reversed correct battery wiring. 1.2.1 PAGE 1.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 135: Vr2 Remote Controller Display

    The control system safety circuits have been activated and the control system has been prevented from moving the wheelchair. This indicates a system trip, i.e. the VR2 has detected a problem somewhere in the wheelchair's electrical system. Please refer to Section 3 (VR2 Controller Diagnostics). SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 2.1...
  • Page 136: Vr 2 Remote & R-Net Led Controller Display .2.2

    An Actuator trip is indicated. If more than one actuator is fi tted, check which actuator is working correctly. Check the actuator wiring. PAGE 2.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 137: R-Net Color Joystick & Omni Controller Display Symbols

    The control system can be locked in one of two ways. 1. using a physical key 2. using a key sequence How the control system is locked depends on how the chair is programmed. Control System Locked SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 2.3...
  • Page 138 Section 2 PAGE 2.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 139: Vr2 Controller Diagnostic Codes

    A3.1.1 Otherwise, check the brushes on the left motor (Figure A3.1.2). Ensure that they are not excessively worn. Replace as required. A3.1.2 SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 3.1...
  • Page 140: Three Bars - Left Motor Wiring Trip)

    If all of the readings are open, then replace the controller. If any of the readings are short, then replace the left motor. A3.2.1 Test 1 Test 2 Test 3 Test 4 PAGE 3.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 141: Four Bars- Right Motor Disconnected

    3.3.1 Otherwise, check the brushes on the right motor (Figure 3.3.2). Ensure that they are not excessively worn. Replace as required. 3.3.2 SUNRISE MEDICAL RHYTHM SERVICE MANUAL 2009 PAGE 3.3...
  • Page 142: Five Bars - Right Motor Wiring Trip

    Seven Bars + Speed Profile Indicator Communication Error Inspect wiring between joystick module and controller. Replace the jumper or joystick module with damaged wiring. If the problem persists replace the controller. PAGE 3.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 143: Eight Bars - Possible Control System Trip

    1 and pin 2 of the charger port of the VR2 controller, see (figure 3.5.2) If the meter reads more than 30 volts, then check the charger. Otherwise, replace your controller. 3.5.2 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 3.5...
  • Page 144 PAGE 3.6 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 145: R-Net Troubleshooting Procedures

    The connectors are designed to visually indicate when they are not mated correctly. If yellow is showing between the halves (A), push them closer together until only black is visible. Retest as necessary. fig. 4.1.2 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 4.1...
  • Page 146 4.2.2 Manually tilt the seat back and remove the shroud from the base. Refer to Battery Removal section of this manual. Disconnect the batteries (fig 4.2.3). fig. 4.2.3 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 4.2...
  • Page 147 (+) terminal of each battery (fi g. 4.3.2). Normal resistance is less than 1 ohm. If open, replace the defective battery harness. Retest as necessary. fig. 4.3.2 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 4.3...
  • Page 148 PAGE 4.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 149: R-Net Fault Codes

    16 ohms. M2 Brake Error Verify that the right motor is connected to the control module. Brake resistance should be approximately 16 ohms. Brake resistance should be approximately 16 ohms. SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 5.1...
  • Page 150: R-Net Fault Codes Cont

    PM Memory Error Recycle the power. Verify that the cables are correctly mated. If a module has been replaced recently, suspect that module may be defective. Contact Sunrise Technical Service for assistance. PAGE 5.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 151: Example Of R-10 Fault Isolation

    Complete the Motor and Gearbox Inspection fig. 5.3.1 section of this manual.” The next step is to complete the Motor and Gearbox Inspection section of this manual and SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 5.3...
  • Page 152 Refer to Tilt Actuator and Micro-Switch Removal section of this manual. If the test passes, replace in this order: Cable leading from tilt to control module. Control module Tilt with Recline: Refer to the recline section of this manual PAGE 5.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 153: Power Chair Will Not Drive In Creep Speed When Tilted

    5.5.2 indication should be open (fi g 5.5.3). If it is closed, replace the micro-switch. Refer to tilt actuator and micro-switch removal section of this manual. Open Re-test as necessary. fig. 5.5.3 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 5.5...
  • Page 154: Tilt Will Not Operate

    (fi g. 5.6.2) and disconnect it. fig. 5.6.2 Select tilt on the hand control and place a rubber band around the joystick to hold it displaced (fi g. 5.6.3). fig. 5.6.3 PAGE 5.6 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 155 (fi g 5.7.3). Or, proceed to step 8. fig. 5.7.2 Apply volt Voltage to power supply to the the actuator Actuator connector pins shown. fig. 5.7.3 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 5.7...
  • Page 156 Continuity between pins may even be high. The value recorded in the other direction is across the open contact of the end of stroke micro-switch and should be fig. 5.8.3 open. PAGE 5.8 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 157: Troubleshooting Recline

    Section 6 Section 5 Troubleshooting Recline Power Recline is offered on the Rhythm. This Powered seating option Offers both Power Recline and Power Shear and its operation is controlled by the ISM (Intelligent Seating Module). Actuator Channels Left Inhibit Lights...
  • Page 158: Troubleshooting Power Recline Calibration

    Inhibit 4 port in the ISM. (fi g. 6.2) Actuator Channels Left Inhibit Lights Inhibit Right Lights fig. 6.2.1 Actuator Channels Check the recline potentiometer resistance at the Inhibit 4 harness as shown. (fi g 6.2.2) fig. 6.2.2 PAGE 6.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 159: Power Chair Will Not Drive In Creep Speed When Reclined

    If the wheelchair is not driving in creep speed when the backrest is reclined more than 110 degrees, refer to the above the recline actuator calibration process. And re-test. If the calibration process does not correct the issue, please contact Sunrise Medical Tech Support. SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 6.3...
  • Page 160: Power Recline Does Not Operate

    (fi g 6.4.2) at pins 1 and 5. ( Fig 6.4.3) If your reading is open, replace the recline actuator. If resistance is verifi ed, replace the harness leading from the 6 pin actuator harness to the ISM. fig. 6.4.3 PAGE 6.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 161: Power Shear Does Not Operate

    (fi g 6.5.2) at pins 1 and 5. If your reading is open, replace the shear actuator. If resistance is verifi ed, replace the harness leading from the 6 pin actuator harness to the ISM. fig. 6.5.2 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 6.5...
  • Page 162 PAGE 6.6 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 163: Troubleshooting Power Legrest

    We are offering two versions of power legrest, Center Mount legrest actuator and Swing away Dual Elevating / Articulating (ELR/ALR). With these new assemblies, the actuator is attached directly to the legrest. Power ELR/ALR Swing-Away Legrest Power Center Mount Legrest SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 7.1...
  • Page 164 If no resistance is found, replace the legrest actuator that is not functioning. If resistance is verifi ed at this actuator connector, replace the harness from the actuator to the ISM. fig. 7.2.1 fig. 7.2.2 PAGE 7.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 165: Seating System Mounting Instructions

    Section 8 Seating System Mounting Instructions Non Tilt Module/Packer Interface SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 8.1...
  • Page 166: Seat To Tilt Mounting

    Section 8 ASAP (Tilt Only) Seating System Mounting Instructions Seat to Tilt Mounting PAGE 8.2 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 167 Section 8 Traditional Rehab Seating System Mounting Instructions Seat to Tilt Mounting SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 8.3...
  • Page 168: Tilt To Interface Mounting

    Section 8 Tilt to Interface Mounting PAGE 8.4 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 169: New Power Recline Seating System Mounting Instructions

    Section 8 New Power Recline Seating System Mounting Instructions Seat to Recline Mounting SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 8.5...
  • Page 170: New Power Tilt & Recline Seating System Mounting Instructions

    Section 8 New Power Tilt & Recline Seating System Mounting Instructions Seat to Tilt/Recline Mounting: fig. 7.7 PAGE 8.6 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 171: Seat To Floor Height Matrix

    Section 8 Seat to Floor Height Matrix Actual STFH dimensions are listed for short confi guration: Add 1” for Med / Add 2” for Tall / add 3” for Extra Tall fig. 7.11 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 8.7...
  • Page 172 T r ansit No M odule 20.4 1 / A No Go No Go No Go No M odule with 20.9 2 / B No Go No Go No Go T r ansit PAGE 8.8 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 173 T r ansit No M odule 20.1 1 / A No Go No Go No Go No M odule with 20.6 2 / B No Go No Go No Go T r ansit SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE...
  • Page 174: Asap Fixed Center Mount Footrest Mounting Matrix

    5/8” R E D S HADE D AR E AS AR E NO-G O’s DE F AULT C ONF IG UR AT E ION F R OM F AC T OR Y PAGE 8.10 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 175: Adjusting Power Elr / Alr Legrest Length

    To better access the top bolt you will need to remove the knee pad fi rst. A 13mm open wrench on the nut and a 13mm socket to remove the knee pad bracket. Fig 8.7 SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 8.11...
  • Page 176 Removing the legrest actuator from the ELR / ALR cont. Use a 13 mm open wrench and a 13mm socket to release the top nut. Fig 8.8 Repeat this process for the bottom nut. Fig 8.9 PAGE 8.12 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 177: Adjusting Power Recline Backrest

    Adjusting Power Recline Backrest Adjustments of the New Recline for seat pan are similar to the old perfect fi t recline. Refer to that portion of the Rhythm and Groove service manual for those procedures. The seat-back angle is adjusted thru a change in programming.
  • Page 178 (fi g 8.4) It is important to also adjust the placement of the recline actuator pivot bracket when seat depth has been changed. See fi g 8.5 PAGE 8.14 RHYTHM SERVICE MANUAL 2009 SUNRISE MEDICAL...
  • Page 179: Obp Programming Quick Guide

    Section 9 OBP Programming Quick Guide SUNRISE MEDICAL 2009 RHYTHM SERVICE MANUAL PAGE 9.1...
  • Page 180 Section 9 OBP Programming Quick Guide PAGE 9.2 RHYTHM SERVICE MANUAL SUNRISE MEDICAL 2009...
  • Page 182 ©2006 Sunrise Medical...

This manual is also suitable for:

Groove

Table of Contents