10.3.4

Connect the cable to the Outdoor Unit

1
Remove the control board cover from the unit by loosening the screw.
2
Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 x
2
1.5 mm
(1.0 ~ 1.5HP) or 4 x 2.5 mm
cord. Do not use joint connection cable. Replace the wire if the existing wire (from concealed wiring, or
otherwise) is too short.
3
Secure the cable onto the control board with the holder (clamper).
4
Attach the control board cover back to the original position with the screw.
5
For wire stripping and connection requirement, refer to instruction 10.2.4 of the indoor unit.
Earth wire shall be Yellow/Green (Y/G) in colour and longer than the other AC wires for safety reason.
10.3.5

Piping Insulation

1
Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation
Diagram. Please wrap the insulated piping end to prevent water from going inside the piping.
2
If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by
using POLY-E-FOAM with thickness 6 mm or above.
2
(2.0 ~ 2.5HP) flexible cord, type designation 245 IEC 57 or heavier