Heating Sequence Of Operation - Lennox 80UGH Unit Information

80uhg series mid−efficiency gas furnaces
Table of Contents

Advertisement

NORMAL HEATING MODE
POWER ON
CONTROL SELF−CHECK OKAY?
YES
IS POLARITY REVERSED?
IS VOLTAGE
ABOVE 75 VOLTS?
ROLLOUT SWITCH CLOSED?
YES
BURNER OFF?
(CONTINUOUS FLAME CHECK)
YES
NO
NORMAL OPERATION:
LED #1 −− SLOW FLASH
LED #2 −− SLOW FLASH
YES
THERMOSTAT CALLS FOR HEAT:
LED #1 −− FAST FLASH
LED #2 −− FAST FLASH
YES
PRIMARY AND SECONDARY LIMIT SWITCH.
CLOSED?
YES
IS COMBUSTION AIR
PRESSURE SWITCH OPEN?
YES
IS COMBUSTION AIR BLOWER
ENERGIZED?
YES
HAS COMBUSTION AIR PRESSURE
SWITCH CLOSED IN 2.5 MINUTES?
YES
CONTINUED NEXT PAGE

HEATING SEQUENCE OF OPERATION

NO
NO
YES
NO
NO
Page 25
ABNORMAL HEATING MODE
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER DELAY OFF.
NO
(RESET CONTROL BY TURNING MAIN POWER OFF.)
YES
POLARITY REVERSED.
LED #1 −− FAST FLASH
LED #2 −− SLOW FLASH
LED SIGNALS WAITING ON CALL FROM
THERMOSTAT. CONTROL WILL NOT RESPOND
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON.
LED #1 −− ON. LED #2 −− SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
INDOOR BLOWER ON HEATING SPEED.
LED #1 −− SLOW FLASH
LED #2 −− OFF
COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER ON
LED #1 SLOW FLASH RATE
NO
COMBUSTION AIR INDUCER OFF.
NO
INDOOR BLOWER OFF WITH DELAY.
LED #2 SLOW FLASH
(Sequence holds until pressure switch
closes or thermostat resets control.)
PRESSURE SWITCH IS IN WATCHGUARD MODE.
NO
GAS VALVE OFF. COMBUSTION AIR INDUCER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 −− OFF. LED #2 −− SLOW FLASH.
IS 5-MINUTE RESET PERIOD COMPLETE?
LED #1 ON
LED #2 ON
LED #2 −− ON
GAS VALVE OFF.
LED #1 OFF