Heating Sequence Of Operation - Lennox DAVE SIGNATURE SL280DFV Installation Instructions Manual

Gas furnace downflow air discharge
Hide thumbs Also See for DAVE SIGNATURE SL280DFV:
Table of Contents

Advertisement

Other Unit Adjustments
Primary and Secondary Limits
The primary limit is located on the heating compartment
vestibule panel. The secondary limits (if equipped) are lo-
cated in the blower compartment, attached to the back
side of the blower. These limits are factory set and require
no adjustment.
Flame Rollout Switch
This manually reset switch is located inside the burner
box. If tripped, check for adequate combustion air before
resetting.
Pressure Switches
The pressure switch assembly (includes two switches) is
located in the heating compartment adjacent to the com-
bustion air inducer. These switches check for proper com-
bustion air inducer operation before allowing ignition trial.
The switches are factory-set and require no adjustment.
Temperature Rise
Place the unit into operation with a second-stage heating
demand. After supply and return air temperatures have
stabilized, check the temperature rise. If necessary, adjust
the heating blower speed to maintain the temperature rise
within the range shown on the unit nameplate. See TABLE
25 on page 56 for allowable heating speeds. Increase
the blower speed to decrease the temperature rise. De-
crease the blower speed to increase the temperature rise.
Failure to properly adjust the temperature rise may cause
erratic limit operation and may result in premature heat
exchanger failure.
Thermostat Heat Anticipation
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.

Heating Sequence of Operation

The two-stage, variable speed integrated control used
in SL280DFV units has an added feature of an internal
Watchguard control. The feature serves as an automat-
ic reset device for ignition control lockout caused by ig-
nition failure. This type of lockout is usually due to low
gas line pressure. After one hour of continuous thermostat
demand for heat, the Watchguard will break and remake
thermostat demand to the furnace and automatically reset
the control to begin the ignition sequence.
NOTE - The integrated control thermostat selection DIP
switch is factory-set in the "TWO-STAGE" position.
Applications Using a Two-Stage Thermostat
See FIGURE 25 for ignition control sequence
A - Heating Sequence -- Integrated Control Thermostat
Selection DIP Switch 1 OFF in "Two-Stage" Position
(Factory Setting)
1 - On a call for heat, thermostat first-stage contacts
close sending a signal to the integrated control. The
integrated control runs a self-diagnostic program
and checks high temperature limit switches for
normally closed contacts and pressure switches for
normally open contacts. The combustion air inducer
is energized at low speed.
2 - Once the control receives a signal that the low
pressure switch has closed, the combustion air
inducer begins a 15-second pre-purge in low speed.
NOTE - If the low fire pressure switch does not close the
combustion air inducer will switch to high fire. After a 15
second pre-purge the high fire pressure switch will close
and the unit will begin operation on high fire. After 10 to
20 seconds of high fire operation the unit will switch to low
fire.
3 - After the pre-purge is complete, a 20-second initial
ignitor warm-up period begins. The combustion air
inducer continues to operate at low speed.
4 - After the 20-second warm-up period has ended,
the gas valve is energized on low fire (first stage)
and ignition occurs. At the same time, the control
module sends a signal to begin an indoor blower
30-second ON-delay. When the delay ends, the
indoor blower motor is energized on the low fire
heating speed, the HUM contacts close energizing
the humidifier and 120V ACC terminal is energized.
The furnace will continue this operation as long as
the thermostat has a first-stage heating demand.
5 - If second-stage heat is required, the thermostat
second- stage heat contacts close and send a signal
to the integrated control. The integrated control
initiates a 30-second second-stage recognition
delay.
6 - At the end of the recognition delay, the integrated
control energizes the combustion air inducer at
high speed. The control also checks the high fire
(second stage) pressure switch to make sure it is
closed. The high fire (second stage) gas valve is
energized and the indoor blower motor is energized
for operation at the high fire heating speed.
7 - When the demand for high fire (second stage) heat
is satisfied, the combustion air inducer is switched
to the low-fire heating speed and the high-fire
(second stage) gas valve is de-energized. The
low-fire (first stage) gas valve continues operation.
The indoor blower motor is switched to the low-fire
heating speed.
8 - When the thermostat demand for low-fire (first
stage) heat is satisfied, the gas valve is de-
energized and the field-selected indoor blower off
delay begins. The combustion air inducer begins a
5-second post-purge period.
9 - When the combustion air post-purge period is
complete, the inducer, the HUM contacts as well
as the 120V ACC terminals are de-energized. The
indoor blower is de-energized at the end of the off
delay.
Page 41

Advertisement

Table of Contents
loading

Table of Contents