10.2 AU48- diagnostic information and trouble shooting
The failure code is displayed on the outdoor PCB; please diagnose the trouble according to the following code:
Failure
code
01
Outdoor
sensor TE circuit
02
Ambient temp. sensor TA
circuit
03
Suction
circuit
04
Discharge temp. sensor TD
circuit
05
Outdoor mid-condenser temp.
sensor
06
Over current
07
Current
circuit
08
Inverter compressor built-in
over-load protection circuit
09
IPM protection
10
EEPROM on PCB faulty
11
Discharge
protection acts (TD)
Pressure sensor (Pd、Ps)
12
wiring faulty
13
Pressure switch circuit
Failure position
defrosting
temp.
temp.
sensor
TS
mutual
inductance
temp.
sensor
Judgment measure
Examine the sensor below 20H in cut circuit or over
1000H in short circuit for continuous 60 seconds,
recoverable
Examine the sensor below 20H in cut circuit or over
1000H in short circuit for continuous 60 seconds,
recoverable
Examine the sensor below 20H in cut circuit or over
1000H in short circuit for continuous 60 seconds,
recoverable
Examine the sensor below 20H in cut circuit or over
1000H in short circuit for continuous 60 seconds after
compressor working for 3 minutes, recoverable
Examine the sensor below 20H in cut circuit or over
1000H in short circuit for continuous 60 seconds,
recoverable
Alarm over current failure, on exceeding current
protection value C for 5 seconds. After occurrence 3
times in 30 minutes, failure code displays on the LED,
unrecoverable
After closing compressor, the current of current
mutual inductance is checked over 15A. when
starting up the compressor, frequency is over 60HZ,
and current is below 5A, recoverable
Inverter compressor built-in over-load protector acts.
IPM over current、short current、temp. too high、lack
of pressure protect alarm 3 times continuously in 30
minutes, unrecoverable
857 reads and writes the data of EEPROM faulty,
flashes 11 times, unrecoverable
Examine TD1 sensor alarms compressor off after 5
seconds at over 120℃, confirming 3 times in
30minutes, and displaying
unrecoverable
After compressor starting up 3 minutes, examine
compressor rate(Pd/Ps) is below 0.9 for continuous
60 seconds, recoverable
High pressure switch acts, trouble disappears after 2
11 on the LED,